E. Auxiliary Inputs/Outputs
Analog Inputs: Two 4-20mA Inputs (10-bit A/D),
240 Ohm Loop Resistance
Configurable as 0-5VDC (10bit A/D)
Integrated Loop Power Supply: +24VDC / 42mA
Aux Digital I/O: Three (3):
Each Configurable as Digital Input or Output
Output(s): TTL (0-5VDC) Output
Input(s): TTL Dry-Contact Input
MODBUS Fn. Codes: 01 - Read Coil Status,
02 - Read Input Status,
03 - Read Holding Registers,
04 - Read Input Registers,
05 - Force Single Coil
06 - Write Single Holding Register
15 - Force Multiple Coils
DF1 Codes: Protected Typed Logical Read With 3 Address Fields
Protected Typed Logical Write With 3 Address Fields
ADAM-4000 Fn. Codes: #AAn - Read Analog Inputs,
(ADAM-Version Only) $AA6 - Read Discrete Inputs,
#AA1n0d - Write Discrete Outputs,
$AAM - Read Device ID
F. Standards and Regulatory Compliances
Safety (USA, Mexico): UL 62368-1 Recognition (MET Labs File No. E112874)
Safety (Canada): CSA C22.2 No. 62368-1 Recognition (MET Labs File No. E112874)
Emissions (USA): FCC Part 15, Class A
Emissions (Canada): ICES-003
Meter Interface: AWWA C707-05
Environmental: ROHS-Compliant, Lead-Free
Manufacturing Location: USA
G. Safety Considerations and Warnings
The following warnings and guidelines should be followed in order to ensure safe operation of your EtherMeter:
• Do not attempt to service the internal circuitry of the EtherMeter. This device contains no user-serviceable
parts or adjustments.
• Carefully inspect the work area in which the EtherMeter will be located to ensure against hazards such as
damp floors, ungrounded power extension cords, and missing ground connections.
Before operating the EtherMeter, ensure that the external power source is an NRTL-listed power supply
that is rated for a DC voltage between 10 and 36 VDC and rated for a minimum current of 275 mA. If you
are not sure of the type of power source, contact SCADAmetrics or your SCADAmetrics Distributor.
The secondary output circuits of the EtherMeter are SELV (Safety Extra Low Voltage). Ensure that the
secondary output circuits are not connected with hazardous energy levels.
• The EtherMeter has been evaluated and NRTL-recognized for use in a Pollution Degree 2 environment.
• The EtherMeter must be examined for compliance with the applicable safety standard after installation into
the final enclosure.
The EtherMeter must be installed in accordance with all applicable local electrical codes.
• If the EtherMeter is exposed to moisture or condensation, disconnect it from the power source immediately
and obtain service assistance.
• If the EtherMeter exhibits unexpected behavior, such as smoking or becoming extremely hot, disconnect it
from power sources immediately and then obtain service assistance.
• Ensure that the EtherMeter’s cover is secure on completion of installation to reduce safety hazards.