SET TO1
N (secs) (Flow Timeout For Fixed dTotal)
IF USING FIXED DTOTAL FLOW CALC METHOD, AND METER HAS NOT
INCREASED, AND TIMEOUT HAS ELAPSED, DISPLAY AND REPORT
FLOW RATE AS ZERO.
VALID RANGE: 1-28800
300
SET TO2
N (secs) (Flow Timeout For Fixed dTotal)
300
SET TYPE1
Meter 1 Protocol Type
AUTO, NEPTUNE, SENSUS, ELSTER, PULSE
When set to AUTO, the EtherMeter runs an AUTO-DETECT sequence to
determine the correct encoder-type protocol (NEPTUNE, SENSUS, ELSTER).
AUTO does not detect pulse-type meters. Therefore, when using a pulse-type
meter, the user should always set TYPE1 to PULSE.
AUTO
SET TYPE2
Meter 2 Protocol Type
AUTO
SET DB1
N (msecs) Debounce Filter Window; VALID RANGE: 0 10000 msecs
(PULSE-TYPE REGISTERS ONLY)
PULSE DURATIONS SHORTER THAN DB1 MSECS ARE IGNORED.
DEBOUNCE FILTER IS DISABLED IF DB1=0.
0
SET DB2
N (msecs) Debounce Filter Window; VALID RANGE: 0 10000 msecs
0
SET PD1
N (PULSE DIVIDER); VALID RANGE: 1 100,000
USED IN CONJUNCTION WITH PS1.
(PULSE-TYPE REGISTERS ONLY)
PS1 (PULSE SCALER) and PD1 (PULSE DIVIDER) ARE PARAMETERS
USED TO SCALE THE PULSE COUNT INTO ENGINEERING UNITS. FOR
EXAMPLE, IF METER 1 EMITS 1431 PULSES PER 1000 GALLONS, THEN
PD1 SHOULD BE SET TO 1431 AND PS1 SHOULD BE SET TO 1000.
1
SET PD2
N (PULSE DIVIDER); VALID RANGE: 1 100,000
USED IN CONJUNCTION WITH PS2.
(PULSE-TYPE REGISTERS ONLY)
1
SET PS1
N (PULSE SCALER); VALID VALUES: 1, 10, 100, 1000, 10000, 100000
USED IN CONJUNCTION WITH PD1.
(PULSE-TYPE REGISTERS ONLY)
PS1 (PULSE SCALER) and PD1 (PULSE DIVIDER) ARE PARAMETERS
USED TO SCALE THE PULSE COUNT INTO ENGINEERING UNITS. FOR
EXAMPLE, IF METER 1 EMITS 1431 PULSES PER 1000 GALLONS, THEN
PD1 SHOULD BE SET TO 1431 AND PS1 SHOULD BE SET TO 1000.
1
SET PS2
N (PULSE SCALER); VALID VALUES: 1, 10, 100, 1000, 10000, 100000
USED IN CONJUNCTION WITH PD2.
(PULSE-TYPE REGISTERS ONLY)
1
SET CNT1
PULSE PRE-SET COUNT; VALID RANGE: 0 999999999
(PULSE-TYPE REGISTERS ONLY)
0
SET CNT2
PULSE PRE-SET COUNT; VALID RANGE: 0 999999999
0
SET SIMULATION
OFF, ON
• ON: ETHERMETER REPORTS METER1 REGISTER AS 12345678, AND
FLOW1 REGISTER TO -12345678. USEFUL FOR OFFLINE TESTING.
NOTE: SIMULATION MODE IS ALWAYS CLEARED AFTER REBOOT.
• OFF: ETHERMETER REPORTS ACTUAL REGISTER CONTENTS.
WHEN SIMULATION=ON, THE SETUP MENU PROMPT IS: SIMUL>
WHEN SIMULATION=OFF, THE SETUP MENU PROMPT IS: CMD>
OFF