EasyManua.ls Logo

SCADAmetrics EtherMeter EM-100 - Auxiliary I;O, Interface, and Protocol Setup

SCADAmetrics EtherMeter EM-100
79 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
45
AUX I/O SETUP
SELECTIONS
DEFAULTS
SET AUX1
DIN, DOUT, PWRSAVHI, PWRSAVLO
DIN:
• DIGITAL INPUT – MAY BE MONITORED BY INTERROGATION FROM
MODBUS, DF1, ETHERNET/IP, OR ADAM MASTER
DOUT:
• DIGITAL OUTPUT FOLLOWS COMMANDS FROM MODBUS OR DF1
(OR ADAM) MASTER
PWRSAVHI:
• DIGITAL OUTPUT GOES “HI” (5V) TO TURN ON CONNECTED RADIO
OR MODEM.
PWRSAVLO:
• DIGITAL OUTPUT GOES “LO” (0V) TO TURN ON CONNECTED RADIO
OR MODEM.
(FOR PWRSAVLO AND PWRSAVHI TIMING DIAGRAMS, SEE SECTION 9,
RADIO INTERFACE.)
DIN
SET AUX2
DOUT, DIN, DUP
DOUT:
• DIGITAL OUTPUT FOLLOWS COMMANDS FROM MODBUS, DF1,
ETHERNET/IP, OR ADAM MASTER
DIN:
• DIGITAL INPUT – MAY BE MONITORED BY INTERROGATION FROM
MODBUS, DF1, ETHERNET/IP, OR ADAM MASTER
DUP:
• CONTROL DUPLEXER OUTPUT FOR SDA, SDAW, RRFD, RRFW.
DIN
SET AUX3
DOUT, DIN, DUP
DOUT:
DIGITAL OUTPUT FOLLOWS COMMANDS FROM MODBUS, DF1,
ETHERNET/IP, OR ADAM MASTER
DIN:
• DIGITAL INPUT – MAY BE MONITORED BY INTERROGATION FROM
MODBUS, DF1, ETHERNET/IP, OR ADAM MASTER
DUP:
CONTROL DUPLEXER OUTPUT FOR SDA, SDAW, RRFD, RRFW
RRF
SET ONTIME
N (secs)
• USED WHEN DOUT1=PWRSAVHI OR PWRSAVLO
• TIME TO LEAVE RADIO ON AFTER THE RECEIPT OF A POLL
REQUEST
ADDRESSED TO THIS DEVICE.
• FOR TIMING DIAGRAM, SEE SECTION 9, RADIO INTERFACE.
60
(1 min)
SET OFFTIME
N (secs)
AFTER RECEIPT OF POLL REQUEST AND AFTER ONTIME ELAPSED,
TIME TO LEAVE RADIO OFF.
• AFTER OFFTIME ELAPSES, RADIO WILL BE TURNED OFF AND
DEVICE
WILL WAIT FOR NEXT POLL REQUEST.
• FOR TIMING DIAGRAM, SEE SECTION 9, RADIO INTERFACE.
21240
(5 hrs,54min)