EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-487V - Page 31

Schweitzer Engineering Laboratories SEL-487V
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Schweitzer Engineering Laboratories, Inc. SEL-487V Data Sheet
31
Battery System Monitoring
Pickup Range: 15–300 Vdc, 1 Vdc steps
Pickup Accuracy: ±3% of setting, ± 2 Vdc (all elements
except dc ripple)
±10% of setting, ± 2 Vdc (dc ripple
element)
Maximum
Pickup/Dropout Time:
±1.5 cycles (all elements except dc ripple)
±1.5 seconds (dc ripple element)
Sampling Rate: 1/8 cycle
Voltage Sag/Swell/Interruption Reporting
Pickup Range
Sag: 10.00%–95.00%
Swell: 105.00%–180.00%
Interruption: 5.00%–95.00%
Recording Rates and Duration
Fast: 4 samples/cycle 4 cycle dur.
Medium: 1 sample/cycle 176 cycle dur.
Slow: 1 sample/64 cycles 4096 cycle dur.
Daily: 1 sample/day Indefinite
Control Functions (SEL-487V-1)
Voltage Control
Dead-Band Range: 10.00–300.00 V sec.
Dead-Band Control
Delay: 1–6000 s
Stall-Time Delay: 1–6000 s
Power Factor Control
Dead-Band Range: 0.01–0.99
Dead-Band Control
Delay: 1–6000 s
Stall-Time Delay: 1–6000 s
Minimum Operating
Power: ±1 W or ±1 VAR sec.
VAR Control
Dead-Band Range: –1000.00 to +1000.00 VAR sec.
Dead-Band Control
Delay: 1–6000 s
Stall-Time Delay: 1–6000 s
Minimum Operating
Power: ±1 W or ±1 VAR sec.
Time-of-Day Control
Minimum Resolution: ±1 minute
Universal Sequencer
Accumulation Period: 1–9999 minutes
Resolution: ±1 minute
Accumulated Value: 0–2147483646
Resolution: ±1

Related product manuals