BATTERY BOX
Your selected battery should be
stored in a high quality plastic or
nylon battery box with a lid that is
designed for this purpose.
LOCATION
In a typical installation, the
Pump Sentry should be
mounted on the wall, above
the sump pit or crock, and in
accordance with all
applicable local electrical
codes.
It should be in close
proximity to a grounded AC
outlet and the battery box
(not closer than 2 feet).
VENTILATION
Do Not block either the fan
or the exit air ports of the
Pump Sentry. Allow at least
2 inches of air clearance on
all sides. Any room in which
the Pump Sentry is mounted
should have adequate
ventilation.
UNDER NO
CIRCUMSTANCES
Should the Pump Sentry be
mounted in a confined area or in
a sump pump pit or crock.
Pump Sentry is not only an
electrical appliance, but also
produces a potentially
dangerous and hazardous
electrical current even when
a power outage occurs. It is
safe when installed and used
properly. Keep children
away.
WARNING! The Pump Sentry has several components with
electrical contacts that switch electrical currents. Opening or
closing any of these electrical contacts can produce a spark that
could ignite an explosive air mixture. To prevent fire or
explosion, do not install the Pump Sentry in any area which
might contain flammable liquids or gases. Do not install Pump
Sentry in the same confined area as the battery box.