GC1100 SEDEMAC
Page | 49
Register
Address
Parameter
Scale Factor
Unit/Interpretation
Bits/ Sign
72
Alarm 9
Auxiliary input e
--
--
13/16-16/16
Auxiliary input f
--
--
9/16-12/16
Auxiliary input g
--
--
5/16-8/16
Auxiliary input h
--
--
1/16-4/16
73
Alarm 10
Gen L1 phase low volt
--
--
13/16-16/16
Gen L1 phase high volt
--
--
9/16-12/16
Gen L2 phase low volt
--
--
5/16-8/16
Gen L2 phase high volt
--
--
1/16-4/16
74
Alarm 11
Gen L3 phase low volt
--
--
13/16-16/16
Gen L3 phase high volt
--
--
9/16-12/16
DG phase rotation
--
--
5/16-8/16
Mains phase rotation
--
--
1/16-4/16
75
Alarm 12
--
Fuel level Open Circuit
--
--
13/16-16/16
V belt broken
--
--
9/16-12/16
Extended over load trip
--
--
5/16-8/16
High oil pressure detected
--
--
1/16-4/16
76
Input output diagnostics
Digital input a
--
--
16/16
Digital input b
--
--
15/16
Digital input c
--
--
14/16
Digital input d
--
--
13/16
Digital input e
--
--
12/16
Digital input f
--
--
11/16
Digital input g
--
--
10/16
Digital input h
--
--
9/16
Digital input i
--
--
8/16
Digital output a
--
--
7/16
Digital output b
--
--
6/16
Digital output c
--
--
5/16
Digital output d
--
--
4/16
Digital output e
--
--
3/16
Digital output f
--
--
2/16
Unimplemented
--
--
1/16
77
DG status
GCU Mode
Config (1)/Run (0)
16/16
Mains Healthy / unhealthy
True (1) / False (0)
15/16