TCD02B0001SE 034070 130220
5
INSTALLATION
WARNING
- To properly set the room temperature, install the programmable thermostat far from heat sources, airstreams or particularly cold
walls (thermal bridges).
If a remote sensor is used, the note is applied to the sensor and not to the programmable thermostat.
- In order to connect the external probe use cables with minimum section of 1,5 mm² and with a maximum length of 15 m. Do not
pass the cables through the pipes where the power lines run.
- If the load controlled by the relay of the programmable thermostat operates with mains voltage, the connection must be made via
an omnipolar switch complying with current standards and with a contact opening of at least 3 mm in each pole.
- Installationandelectricalwiringsofthisappliancemustbemadebyqualiedtechniciansandincompliancewiththecurrent
standards.
- Before wiring the device be sure to turn the mains power off.
WIRINGS
Relay output Remote sensor input
Remote
sensor cable
entrance
Relay
output cable
entrance
Boiler
Remote
sensor
(optional)
----: Reinforced insulation.
Circulation pump /
Solenoid valve
----: Reinforced insulation.
Remote
sensor
(optional)
PELLET STOVE CONTROL
The programmable thermostat can be set to regulate the room temperature for turning on and off a pellet stove.
The relay output must be connected to the input for the activation/deactivation of the pellet stove.
Aiming to limit the on/off switches number of the stove, set the parameters as shown below:
- HYSt: Room temperature regulation hysteresis at 1,0°C
- tMIn: Minimum relay acrivation time at 30 minutes