11
TDST24M000SE 032635 190619
Hysteresis of the safety temperatures
Data Regulation range Default
HYTS 1.0 .. 15.0 °C 2.0 °C
Thermostatic hysteresis
Data Regulation range Default
HYT 1.0 .. 15.0 °C 2.0 °C
Probe Offset
Data Regulation range Default
OS1 -5.0 .. +5.0 °C 0.0 °C
OS2 -5.0 .. +5.0 °C 0.0 °C
OS3 -5.0 .. +5.0 °C 0.0 °C
Maximum temperature of the probes S2 (TM2) o S3 (TM3)
Data Regulation range Default
TM2 20.0 .. 90.0 °C 70.0 °C
TM3 20.0 .. 90.0 °C 70.0 °C
WARNING!
It is not possible to set the Maximum Temperature (TM)
to a value higher than the relevant Safety Temperature,
as the Maximum Temperature value is limited to the
value of the Safety Temperature (TS) -5°C.
To increase the Maximum Temperature value, it is
rst necessary to increase the value of the Safety
Temperature.
Integration Temperature (After Heating) on probe S3
Data Regulation range Default
TAH 20.0 .. 90.0 °C 45.0 °C
WARNING!
It is not possible to set the value of the integration
temperature (TAH) at a value which is higher than
the Maximum Temperature (TM3) because the value
of the integration temperature (TAH) is linked to the
Maximum Temperature (TM3) -5°C.
In order to lower the value of the Maximum
Temperature (TM3) below the value of the integration
temperature (TAH) already set, rst of all lower the
value of the integration temperature (TAH), then
change the Maximum Temperature (TM3).
ABC Temperature (Automatic Boiler Control) on probe
S3
Data Regulation range Default
TABC 20.0 .. 80.0 °C 30.0 °C