3.3__GENERAL SETTINGS
Press the
Enter and Esc
keys
at the same time. Value Programming:
Programming Menu (
Default parameters
)
Language
Language setting
UK
Set Point 1
Set Point value
7.4 pH
Type of dosing
Acid
Hysteresis
0.0 pH
Delay St
art
OFF
Delay End
OFF
Set Point 2
Set Point value
7.4 pH
Type of dosing
Acid
Hysteresis
0.0 pH
Delay Start
OFF
Delay End
OFF
Temperature (*)
Measurement unit
°C
Manual
Value
25 °C
mA Output
Range 0/4÷20 mA
4÷20 mA
Value for 0 / 4 mA
Value 0
pH
Value for 20 mA
Value 14 pH
Advanced
Select pH/Redox
pH
Calibration enabled or disabled
Enabled = ON
Instrument reset
Restore default values
Password
0000
3.4__Programming menu detailed settings
Press the Enter and Esc keys together for 5 seco
nds to access the instrument’s programming menu.
Language menu:
Set the desired language from the following:
Italian
English
French
Spanish
German
Set Point 1 menu
: Set the dosing parameters; all settings will be activated by Relay 1.
The menu conta
ins the following items:
Item
Default
Limits
Set Point value
7.4 pH / 750 mV
0÷14 pH / ±1000 mV
Type of dosing
Acid / Low
Acid or Alkaline/High or Low
Hysteresis
0.0 pH / 0 mV
0÷3 pH / 300 mV
Delay Start
OFF
OFF…3÷960 seconds
Delay End
OFF
OFF…
960 seconds
Set Point 2 menu:
Set the dosing parameters; all settings will be activated by Relay 2.
The menu contains the same items as Set Point 1
Temperature menu:
Set the temperature for automatic compensation of the pH measurement. The measurement u
nit may also
be set.