EasyManua.ls Logo

Selema 65 - 2.10 Limit switch inputs

Default Icon
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17
www.selema.it
Service Manual
DC 4Q A Series
t's possible to enable clockwise (CW) and counter-clockwise (CCW) motor rotation by connecting
the +L.SW and -L.SW inputs.
They may be used to block motor rotation when the machines overflow contact is intercepted.
The Enable input in regards to this input always has priority. To enable such a function, you
must:
-- Open soldiering point SG and SH (see figure 1)
-- Then connect on said input a positive voltage (between +5Vdc and + 24Vdc) coming from -for
example two N.C. contacts (see figure 2 or 3)
Function: At opening one of the following contacts you enable the motor rotation in the
corresponding direction.
2.10 Limit switch inputs
Note:
- This Drive is factory set with the SG and SH solder bridge close
- DON'T connect any voltage in the +L.SW and -L.SW inputs if the soldiering point SG and SH are
closed
- When one of these said contacts is intercepted the motor stops with the required inertia.
Fig. 1
Fig. 2
Example with external positive voltage
(between +5Vdc and +24Vdc)

Related product manuals