LINE VOLTAGE
WALL SWITCH SENSORS
INSTALLATION & OPERATION INSTRUCTIONS
MODEL # PIR ACOUSTIC PHOTOCELL DEFAULT MODE
SWX-101-xx* OCC
SWX-103-xx VAC
SWX-104-xx VAC
SWX-111-xx OCC
SWX-113-xx VAC
SWX-121-xx OCC
SWX-123-xx VAC
SWX-124-xx VAC
SWX-131-xx OCC
SWX-133-xx VAC
OVERVIEW
SENSORWORX wall switch sensors detect movement in the infrared energy that
radiates from occupants as they move within the devices eld-of-view. Once occupancy
is identied, the sensor’s internal relay switches power on to the connected lighting.
Units can also be congured to operate in Vacancy Mode (e.g., require lights be manually
switched on). Once lights are on and if equipped with passive dual technology (PIR/
Acoustic), the unit’s microphone is enabled to further enhance detection. An internal timer
is set to keep lights on during brief periods of inactivity and is reset every time occupancy
is signaled by either the passive infrared or acoustic detection technologies. Ambient
daylight detection can also be enabled in the unit so that lights are held off in rooms with
sufcient light contribution from windows or skylights.
SPECIFICATIONS
ELECTRICAL
OPERATING VOLTAGE
120/277 VAC, 50/60 Hz
LOAD RATINGS
MAX: 800W @ 120VAC
1200W @ 277VAC
MIN: None
LOAD TYPES
LED Driver/Lamps
CFL, Electronic/Magnetic Ballasts
(Fluorescent)
Tungsten (Incandescent)
PHYSICAL
SIZE
2.74”H x 1.68”W x 1.39”D
(6.96 x 4.27 x 3.53 cm)
Not Including Mounting Strap
WEIGHT
4.5 oz
MOUNTING
Single Gang Switch Box
ENVIRONMENTAL
OPERATING TEMP
32°F to 122°F (0°C to 50°C)
RELATIVE HUMIDITY
0-95% Non-Condensing,
Indoor Use Only
CODE COMPLIANCE
Wall Switch sensors can be used to
meet many requirements of ASHRAE
90.1(2016), IECC (2015), and Title 24
(2016). In particular, Manual On
(e.g., Vacancy) operation is prescribed
for many building spaces.
FEATURES
ELECTRICAL FEATURES
Interchangeable Line & Load Wires -
Impossible to Wire Backwards
Accommodates Neutral (3-wire)
and No-Neutral (2-Wire) Installation
Electronically Timed Switching
Ensures Long Relay Life
Compatible with LED, Fluorescent
and Incandescent Lighting
Meets NEC Guidelines Regarding
Current Leakage
PHYSICAL FEATURES
Enclosure is 25-40% Shallower than
Other Sensors (< 1” depth into wallbox)
Unique Bat-Wing Shaped Lens Provides
Enhanced Peripheral Detection
Self-Grounding Mounting Strap
Modern Look and Intuitive
Easy-Tap Button
Rugged Vandal Resistant Lens
Settings are Adjustable Without Removing
Cover Plate
OPERATIONAL FEATURES
Wall-To-Wall Passive Infrared
Small Motion Detection
Passive Acoustic Detection (Optional) -
Prevents False Offs when No Motion is Present
100% Passive Detection Methods -
No Interference Potential from External Devices
Ambient Daylight Override Mode Increases
Energy Savings
Congurable Time Delays and Operating Modes
Blue Locator LED when Ligths are Off
* xx = color (WH, IV, AL, GY)
Question and Answer IconNeed help?

Do you have a question about the SENSORWORX SWX-101 Series and is the answer not in the manual?

Summary

Sensorworx Wall Switch Sensor Guide

Overview of Sensorworx Wall Switch Sensors

General introduction to Sensorworx wall switch occupancy and vacancy sensors.

Technical Specifications

Details on electrical, environmental, physical, and code compliance for the sensors.

Key Product Features

Highlights electrical, physical, and operational features of the wall switch sensors.

Coverage and Installation Procedures

Sensor Coverage Area

Describes the detection range, motion detection capabilities, and acoustic coverage.

Wiring and Installation Guide

Instructions for standard and 3-way wiring, including safety precautions.

Mounting and Configuration Settings

Wall Box Mounting Instructions

Guidance on mounting the sensor in single or multi-gang wall boxes.

Configuration Settings Overview

Steps to access and modify sensor settings like time delays and modes.

Occupancy Time Delay Settings

Configures the time the lights remain on after occupancy is detected.

Operational Modes Configuration

Sets the sensor's behavior: Vacancy, Occupancy, Override, Presentation modes.

Ambient Light Override Settings

Configures the photocell to prevent lights turning on if ambient light is sufficient.

Auto-Sensitivity Settings

Adjusts the PIR sensitivity for initial detection when lights are off.

Microphone Settings

Adjusts the acoustic sensor sensitivity or disables it.

LED Functionality Settings

Controls the blue locator LED and white motion indicator LEDs.

Factory Reset Procedure

Restores the sensor to its original factory default settings.

Operational Notes and Modes

Test Mode Operation

Enables a 5-second time delay for efficient walk testing.

Vacancy Mode Specifics

Details on ambient light override and grace period behavior in Vacancy mode.

Microphone Grace Timer

Keeps the microphone active for 10 seconds after lights turn off for reactivation.