3-15
AY-ZP35PR
<INDOOR UNIT>     :1-second ON / 1-second OFF
Problem 
symptom
Outdoor 
unit indi-
cation 
(LED1)
Indoor unit Malfunc-
tion No.
Content of diagnosis Check point Action
Lamp Main Sub Main Sub
Normal con-
dition
Normal 
blinking
Timer (Orange) 0 0 Normal
Operation (Green)
Plasmacluster 
(Blue)
Indoor and 
outdoor units 
do not oper-
ate.
1-time
Timer (Orange) 1 0 Outdoor unit 
thermistor 
short-circuit
Heat exchanger 
thermistor short 
circuit error
(1) Measure the resis-
tance of the outdoor 
unit thermistors. 
(1) Replace the out-
door unit ther-
mistor assembly.
Operation (Green)
Plasmacluster 
(Blue)
Timer (Orange) 1 Outdoor temper-
ature thermistor 
short circuit error
(2) Check the lead wire 
of the outdoor unit 
thermistor for torn 
sheath and shortcir-
cuit.
(2) Replace the out-
door unit ther-
mistor assembly.
Operation (Green)
Plasmacluster 
(Blue)
Timer (Orange) 2 Suction ther-
mistor short cir-
cuit error
(3)  No abnormality 
found in above 
inspections (1) and 
(2).
(3) Replace the out-
door unit control 
PWB assembly.
Operation (Green)
Plasmacluster 
(Blue)
Timer (Orange) 3 2-way valve
thermistor short
circuit error
Operation (Green)
Plasmacluster 
(Blue)
Indoor and 
outdoor units 
do not oper-
ate.
2-time
Timer (Orange) 2 0 Cycle tem-
perature
Compressor high 
temperature 
error
(1) Check the outdoor 
unit air outlet for 
blockage.
(1) Ensure unob-
structed air flow 
from the outdoor 
unit air outlet.
Operation (Green)
Plasmacluster 
(Blue)
(2) Check if the power 
supply voltage is AC 
230V at full power.
(2) Connect power 
supply of proper 
voltage.
(3) Check the pipe con-
nections for refriger-
ant leaks.
(3) Charge the speci-
fied amount of 
refrigerant.
(4) Measure resistance 
of the outdoor unit 
compressor ther-
mistor.
(4) Replace the out-
door unit compres-
sor thermistor 
assembly.
(5) Check the expansion 
valve for proper 
operation.
(5) Replace the
expansion valve 
coil, expansion 
valve or outdoor 
unit control PWB 
assembly.
Indoor unit 
operates.
Outdoor unit 
does not 
operate tem-
porarily. 
Timer (Orange) 1 Compressor dis-
charge overheat.
(Temporary stop for cycle 
protection)
-
Operation (Green)
Plasmacluster 
(Blue)
Timer (Orange) 2 Outdoor unit heat 
exchanger over-
heat.
(Temporary stop for cycle 
protection)
-
Operation (Green)
Plasmacluster 
(Blue)
Timer (Orange) 3 Indoor unit heat 
exchanger over-
heat.
(Temporary stop for cycle 
protection)
-
Operation (Green)
Plasmacluster 
(Blue)
Timer (Orange) 4 IPM high temper-
ature error
(Temporary stop for cycle 
protection)
-
Operation (Green)
Plasmacluster 
(Blue)
Indoor and 
outdoor units 
do not oper-
ate.
Timer (Orange) 5 IPM high temper-
ature error
(1) Measure resistance 
of the heat-sink ther-
mistor.
(1) Replace the out-
door unit PFCM 
PWB or control 
PWB assembly or 
change the heat-
sink thermistor.
Operation (Green)
Plasmacluster 
(Blue)
[9] CHART