Alarm: Lower limit of a
flow rate
0x009A ~ 0x009B
Set alarm value for a lower flow rate limit
Notes
Alarm values = Value (0x009A)*65536 + Value (0x009B)
When the flow rate is below a set value, an alarm will be triggered.
Change password 0x00AE ~ 0x00AF
Change the default password
Notes
Password values = Value (0x00AE)*65536 + Value (0x00AF)
Available: 00000 ~ 99999
Offset calibration 0x00F0
Reset or calibrate the offset
Notes
To reset or calibrate the offset, write 0xAA55 to register 0x00
When you execute this function, make sure there is NO flow in the flow
channel.
Reset accumulated
flow rate
0x00F2
Reset the accumulated or totalized flow rate value
NT 16, Fixed value 0x0001
Notes
To reset the accumulated or totalized flow rate value, write 0x0001 to register
0x00F2.
Write protection 0x00FF
Write protection disabler for a set value to a specific register.
Notes
abled at the time of product shipment. To enable the write
function of a specific parameter, such as GCF, the user needs to send 0xAA55
to the register 0x00FF, and then the write function will be enabled (write
protection is disabled). After the write execution is completed, the firmware
will automatically re-enable the write protection.