User’s Manual 19
Conditions for its
activation
No block
Engine running
Generator already in the operating window from starting.
Shutdown cycle not in progress
Fuel solenoid activated
With selector on MAN, generator set contactor closed
Generator’s voltage under the threshold set through the
parameter P13 at least on one phase
Not existent in asynchronous engine version
Time set through the parameter P24
Message “F01” on the display “MULTIFUNCTION”
Conditions for its
activation
No block
Engine running
Generator already in the window from starting.
Shutdown cycle not in progress
Fuel solenoid activated
With selector on MAN, generator set contactor closed
Generator’s frequency under the threshold set through the
parameter P11
Not existent in asynchronous engine version
Time set through the parameter P23
Message “F03” on the display “MULTIFUNCTION”
Conditions for its
activation
“EMERGENCY STOP” input, terminal 03 open
Indicator “EMERGENCY STOP” slowly flashing