18 User’s Manual
Bit 4 of the Parameter P49 = 0
Conditions for its
activation
Digital “INPUT B” (terminal 13) shorted to ground
Time set through the parameter P40
Message “F10” on the display “MULTIFUNCTION”
Conditions for its
activation
AUTO o TEST mode. Bit 1 of parameter P61 = 1 (KR status
connected to INPUT C). KR command active.
Time set through the parameter P75
Message “F13” on the display “MULTIFUNCTION”
Starting from revision 08.00.24 (not available for /P version and for asynchronous engine
version). Setting bit 5 of P61 at 1, it is activated a function that switch the load to Generator
set, keeping it running, in case of F13 alarm.
Starting from revision 08.00.38, this block may be masked if mains is not present by using bit
one of parameter P79.
Conditions for its
activation
AUTO o TEST mode. Bit 0 of parameter P61 = 1 (KG status
connected to INPUT A). KG command active.
Time set through the parameter P75
Message “F14” on the display “MULTIFUNCTION”
Starting from revision 08.00.24.
Board without power measure option, otherwise
Parameter P56 = 0
Parameter P58 = 0
Parameter P56 >= P58
Bit 7 of parameter P61 = 0
Conditions for its
activation
Active power higher than P58 threshold (see paragraph 7.6.2)
Time set through the parameter P59
Message “F49” on the display “MULTIFUNCTION”
This warning is present only from software release EB02200080037.