GC310, GC350, GC500, GC500Plus and GC500Mains User’s Manual 17
Page M.06 displays partial energy and total energy meters (active and reactive energy).
Page M.07 (only available when the AT - amperometric transformer - configuration is set to Use) displays partial
and total energy meters (active and reactive energy).
Page M.08 GC500/GC500
Plus
/GC500
Mains
displays the single-line diagram of the plant. The elements displayed
depend on the type of plant.
3.4.4
This mode shows the measurements of the engine operation parameters.
Page E.01 displays the main engine measurements (oil pressure - bar -, coolant temperature - °C - and
r.p.m.).
Page E.02 displays the start-up battery voltage (V) and the fuel level (%).
Page E.03 displays the start-up and operating hours counter (partial and total operation hours, hours under
load, Override hours, remaining hours to the next service).
Number of displayed pages can vary depending on the engine type (J1939, MTU o without communication
interface).
Pages E.04, E.05, E.06, E.06 (only available with CANBUS configuration enabled) display measures acquired
through CANBUS.
Note: Depending on engine models some parameters may not be displayed.
Pages E.10, E.11, E.12 (only available if configured) display measures acquired by the controller and
configured as generic sensor.
3.4.5
Plus Mains
Page B.01 displays voltage and frequency measurements related to the generator and to the mains/bus.
Page B.02 displays synchronization information. Using the displayed synchronoscope in MAN mode, allows
you to perform manual synchronization (refer to par. 3.5.1).
Page B.03 displays the parameters used to monitor parallel operation. This windows allows you to change the
power supplied in the mains parallel applications in BASE LOAD and IMPORT/EXPORT operation.
Page B.04 displays information about mains control cards (e.g. MC100).
Pages B.05, B.06, B.07 display PMC-Bus line related information (active and reactive power, total active and
reactive energy meters) and active and reactive power measurements for each individual generator.
Pages B.08, B.09 display information about load function. These ones include the number of devices connected
to the mains, the operating mode of the load function, the identifier of the pilot generator and the priority list.
For load function configuration refer to EAAM0322XX (Parameters table).
3.4.6
This mode allows you to access events and data log display.
A number and time and date stamp identifies each record.
The number shows in the top right line of the multifunctional display with the total number of records.
When the archive is full, a new record overwrites the old one so that the identification number may change in
time.