IO-Link ports
Tightening torque = 0.6Nm
The length of cable of the sensor and actuator lines is generally limited to 30m.
If an IO-Link connection is active, the length of cable is limited to max. 20m.
Table 5: IO-Link ports (S1 – S8): M12 female contact, A-coded, port class A/B
PIN IO-Link port class A IO-Link port class B1
1)
Pin 1 L + (U
s
+) L + (U
s
+)
Pin 2 DI/DO 2L + (U
A
+)
Pin 3 L - (U
s
-) L - (U
s
-)
Pin 4 IO-Link/DI/DO IO-Link/DI/DO
Pin 5 L - (U
s
-) L - (U
s
-)
21
4
3
5
1)
No galvanic separation
Ethernet ports
Tightening torque = 0.6Nm
Table 6: Ethernet ports (P1 – P2): M12 female contact, D-coded
PIN Description
Pin 1 Tx +
Pin 2 Rx +
Pin 3 Tx -
Pin 4 Rx -
Pin 5 n. c.
3
2
4
1
5
Supply ports
US: 18 ... 30V DC
UA: 18 … 30V DC
Tightening torque = 0.6Nm
Table 7: Power ports (PWR1 – PWR2): M12 male connector/female contact, L-coded
PIN
Description
Pin 1 +24V DC US
Pin 2 0V
Pin 3 0V
Pin 4 +24V DC UA
Pin 5 GND
ELECTRICAL INSTALLATION 6