EasyManua.ls Logo

SICK EtherCAT SIG350

SICK EtherCAT SIG350
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Ethernet
Table 30: Ethernet
Ethernet interface 2x100 Base-Tx (with switch)
Cable type according to
IEEE 802.3
Min. STP CAT 5 /ST CAT 5e
Data transmission rate 100Mbit/s
Max. cable length 100m
Flow control Half duplex/Full duplex (IEEE802.33x-Pause)
Open TCP ports 80 (HTTP)
1883 (MQTT)
2122 (SOPAS)
4840 (OPC UA)
44818 (Ethernet/IP Encapsulation messages based on TCP
Explicit messaging)
50111 (Open for 30 seconds after power up)
Open UDP ports 68 (DHCP Client)
161 (SNMP Server)
2222 (implied messages IO)
30718 (CoLa scan receiver)
30719... 30738 (CoLa scan sender: if a port is blocked by the
application, the next port is used).
34964 (Profinet RPC Endpointmapper)
44818 (Ethernet/IP Encapsulation messages based on UDP)
49152 (Profinet RPC Device Server)
MQTT version V3.1.1
Additional information:
Table 31: Additional information
Max. number of I/Os that
can be connected:
104 E/As (8 + 8x6x2 combined with SIG100)
Max. number of I/O-Link
signals that can be con‐
nected:
8
Ethernet ports: 2
Max. switching frequency: 50Hz
IO-Link
Table 32: IO-Link
Specification
V1.0.0 ... V1.1.3
Connection class Class A
Class
1)
Transmission rate COM1/COM2/COM3
Min. IO-Link cycle time 1ms
Detection of transmission
rate
Automatic
1)
Class B is achieved by using pin 2 as output for the voltage supply. Freely configurable per port, no
galvanic separation between US and UA.
TECHNICAL DATA 12
8027836./2022-06-10 | SICK O P E R A T I N G I N S T R U C T I O N S | Sensor Integration Gateway - SIG350