EasyManua.ls Logo

SICK ReLy HAND1 - Terminals on Front Connector

SICK ReLy HAND1
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Pin assignment
1
3
7
9
11
13
15
2
4
8
10
12
14
16
1
Figure 10: Terminals on front connector
1
Safe isolation of the enabling current paths from the other terminals
Table 5: Pin assignment of the terminals
Terminal Description
13, 14 Enabling current path
23, 24 Enabling current path
I1 Safety capable input for control device A, normally open
I2 Safety capable input for control device A, normally closed
I3 Safety capable input for control device B, normally open
I4 Safety capable input for control device B, normally closed
S1
1)
External device monitoring input (EDM)
Y1 Application diagnostic output (NC)
A1 24V DC voltage supply
A2 Voltage supply 0VDC
1)
Use w
ith external device monitoring (EDM): Connect N/C contacts of the controlled actuators
between voltage supply U
V
and S1.
Use without external device monitoring (EDM): Connect U
V
and S1 with a wire jumper.
Complementary information
T
o protect and increase the service life of contact outputs, equip all connected loads
with varistors or RC elements. The response times will increase depending on the
suppressor used.
Further topics
"C
onnection diagrams", page 15
"Data sheet", page 25
"Electrical integration", page 13
ELECTRICAL INSTALLATION 6
8020872/1FH0/2022-10-27 | SICK O P E R A T I N G I N S T R U C T I O N S | ReLy HAND1
21
Subject to change without notice

Table of Contents

Related product manuals