EasyManua.ls Logo

SICK ReLy HAND1 - Technical data; Data sheet

SICK ReLy HAND1
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 Technical data
10.1 Data sheet
Safety-related parameters
T
he required safety-related characteristic value depends on the application.
Table 7: Safety-related parameters
Safety integrity level
(IE
C61508)
SIL3 SIL2 SIL1
SIL claim limit
(IEC62061)
SIL3 SIL2 SIL1
Cate‐
gory(ISO13849-1)
4 3 3
Performance level (ISO
13849-1)
PLe PL d PL c
Hardware error toler‐
ance
1
Maximum test interval
of t
he safety function
1month 1year
MTTF
D
(single chan‐
nel) (ISO13849-1)
1)
300years 100years 100years
PFH
D
(me
an probability of a dangerous failure per hour)
1)
For operating
hei
ghts≤2,000m
above sea level
1 × 10
-9
1 × 10
-8
1 × 10
-7
For operating
heights2,000...
4,000m above sea
level
5 × 10
-9
5 × 10
-8
1 × 10
-7
PFD
a
vg
(mean probability of a dangerous failure on demand)
For operating
hei
ghts≤2,000m
above sea level
5 × 10
-5
5 × 10
-4
5 × 10
-3
For operating
heights2,000...
4,000m above sea
level
2.5 × 10
-4
2.5 × 10
-3
5 × 10
-3
T
M
(mission time) 20years (ISO 13849-1)
Safe status when a
f
ault occurs
The normally open is open; in other words, the safety-related enabling
current paths are interrupted.
Stop category 0 (IEC60204-1)
1)
To achieve the safety-related characteristic values, the service life curve of the safety contacts must be
t
aken into consideration.
The maximum number of switching operations should be applied to the mission time T
M
.
Mean number of switching operations per year = switching operations based on the service life curve/T
M
As long as the mean number of allowed switching operations per year and the number of allowed
switching operations during the mission time T
M
has not been reached, the safety-related characteristic
values do not depend on the switching frequency if the service life curve is adhered to. B10
d
has already
been taken into consideration when calculating the safety-related characteristic values.
Service life curve, see figure 12, page 30
TECHNICAL DATA 10
8020872/1FH0/2022-10-27 | SICK O P E R A T I N G I N S T R U C T I O N S | ReLy HAND1
25
Subject to change without notice

Table of Contents

Related product manuals