Description The input signal is delayed by the configured time.
Number of inputs 1
Input data type 1-bit
Input description input: input value
Number of outputs 1
Output data type 1-bit
Output description output: when the input becomes true, the output becomes
true after a preset time delay. The output remains true as long
as the input is true. When the input is false or becomes false,
the output becomes false with no delay.
Settings OnDelay: Set delay for a rising edge transmitted to the output
(Default 1 ms)
OffDelay: Set delay for a falling edge transmitted to the output
(Default 1 ms)
The may. delay value for one delay is: 65535 ms
The falling edge is configured with the OffDelay setting.
Description Measures the pulse time of the digital input signal triggered
by the rising or falling edge depending on the configuration.
Information: There is no reset. Once it reaches the High Limit
it stops.
Number of inputs 2
Input data type Input 1 ("Activate"): 1-bit
Input 2 ("Reset"): 1-bit
Input description input: input signal
Reset: Sets the timer to 0 at rising edge
Number of outputs 3
Output data type Output 1 ("High"): 1-bit
Output 2 ("Time"): UInteger 32
Output 3 ("Low"): 1-bit
Output description low: This output is active when the time output is lower than
LowLimit (Information: The 1 ms option is not available).
time: This value increments once per TimeBase whenever
input is active.
high: This output is active when the time output is higher than
the HighLimit.
Settings EnableMode: To activate the mode to specify which time is to
be measured. Selection between rising and falling edge of the
input signal or between falling and rising edge (default: rising
edge).
TimeBase: To select the time base for the time measurement
(default: 100ms)
TimerMode (available from FW 1.3): If in StopWatch mode,
the input is deactivated, the timer pauses at the current
value. The timer can be restarted by activating the input. In
timer mode, the value is reset to 0 when the input signal
becomes active.
HighLimit: Defines an upper value for the Boolean output
signal that is set when the timer value exceeds the defined
upper limit (default: 0).
LowLimit: Defines a lower value for the Boolean output signal
that is set when the timer value falls below the defined lower
limit (default: 0).
8 DEVICE FUNCTIONS
86
O P E R A T I N G I N S T R U C T I O N | Sensor Integration Gateway - SIG200 8024482.1FJ7 /2022-05-31 | SICK