8 2539244105-06
3ZW1012-0SV81-0AA0
6HWWLQJV3DUDPHWULHUHQ3DUDPpWUDJH3DUDPHWUL]DU卣㚏⺷䁥
Differenzansprechstrom IΔn einstellen / Set residual operating current IΔn / Réglage du courant de fonc
-
tionnement différentiel IΔn / Ajuste de la sensibilidad IΔn / Impostazione della corrente differenziale di inter
-
vento IΔn / Definir a corrente de resposta diferencial IΔn / Diferansiyel tepki akımının IΔn ayarlanması /
Настройка разностного тока срабатывания IΔn / Ustawianie prądu różnicowego zadziałania IΔn / 设置
动动作电流 IΔn
PROG
PROG
PROG
30 mA
30 mA
1.0V
SAVE
30 mA
100 mA
30 mA - 100 mA - 300 mA -
500 mA - 1,0 A -
2,0 A - 3,0 A
30 mAINS
0 mA
100 mAINS
0 mA
V
DE Nach 5s Inaktivität wird die aktuelle Einstellung gespeichert.
EN After 5 seconds of inactivity the present setting is saved.
Verzögerungszeit Δt einstellen / Set delay time Δt / Réglage de la temporisation Δt / Ajuste del retardo Δt /
Impostazione del tempo di ritardo Δt / Definir o tempo de retardo Δt / Gecikme süresinin Δt ayarlanması /
Настройка времени запаздыванияΔt / Ustawianie czasu opóźnienia Δt /
设置延迟时间 Δt
PROG
PROG
PROG
INS
INS
1.0
V
SAVE
INS
60 ms
INS - SEL - 60 ms - 100 ms-
200 ms - 300 ms - 400 ms -
500 ms - 750 ms - 1, 0 s - 3,0
s - 5,0 s - 10 s
30 mA60ms
0.0 A
30 mAINS
0.0 A
V
DE Nach 5s Inaktivität wird die aktuelle Einstellung gespeichert.
EN After 5 seconds of inactivity the present setting is saved.
DE INS: unverzögert; SEL: selektiv
EN INS: instantaneous, SEL: selective
IΔn = 30 mA -> INS
IΔn > 30 mA -> INS-10s