Commissioning a project 
  6.6 OS update - Basic Panel DP 
Basic Panels 
Operating Instructions, 04/2012, A5E02421799-03 
101 
Restoring the data of the HMI device  
Proceed as follows:  
1.  Select the "Restore" command from the "Online > HMI device maintenance" menu. 
2.  Enter the name of the backup file under "Save as". 
Information about the selected backup file is displayed under "Content".  
3.  Click "Start Restore". 
This starts the restoration. This operation takes some time, depending on the connection 
selected.  
6.6  OS update - Basic Panel DP 
6.6.1  Overview 
Updating the operating system 
A compatibility conflict may occur when transferring a project to the HMI device. This is 
caused by different versions of the configuration software used and the HMI device image 
available on the HMI device. If there are different versions, the transfer is aborted. A 
message indicating a compatibility conflict is displayed on the configuring PC. 
There are two ways to match the versions: 
●  Update the HMI device image if the project was created with the most recent version of 
the configuration software. 
●  Transfer a matching version of the HMI device image if you do not want to adapt the 
project for the HMI device to the most recent version of the configuration software for the 
project. 
NOTICE 
 
 
Data loss 
All data on the HMI device, such as the project and licenses, will be deleted when you 
update the operating system. 
 
 
Note 
Calibrating the touch screen 
After the update, you may have to recalibrate the touch screen.