Analog input module SM 331; AI 6 x TC Isolated (6ES7331‑7PE10‑0AB0)
30 A5E02398493-02, 11/2008
Measuring Methods and Measuring Ranges
The following table contains all the measuring methods and measuring ranges of the module and its codes. You must enter
these codes in the corresponding bytes of data record 1
(see Figure User Calibration Function).
Measurement Type Code Measurement Range Code
Deactivated 2#0000 Deactivated 2#0000
Voltage 2#0001 ± 80 mV
± 250 mV
± 500 mV
± 1 V
± 25 mV
± 50 mV
2#0001
2#0010
2#0011
2#0100
2#1010
2#1011
Thermocouple, linearization,
reference temperature 0° C
2#1010 B
N
E
R
S
J
L
T
K
U
C
TxK/XK(L)
2#0000
2#0001
2#0010
2#0011
2#0100
2#0101
2#0110
2#0111
2#1000
2#1001
2#1010
2#1011
Thermocouple, linearization,
reference temperature 50° C
2#1011 B
N
E
R
S
J
L
T
K
U
C
TxK/XK(L)
2#0000
2#0001
2#0010
2#0011
2#0100
2#0101
2#0110
2#0111
2#1000
2#1001
2#1010
2#1011
Thermocouple, linearization, internal
comparison
2#1101 B
N
E
R
S
J
L
T
K
U
C
TxK/XK(L)
2#0000
2#0001
2#0010
2#0011
2#0100
2#0101
2#0110
2#0111
2#1000
2#1001
2#1010
2#1011
Thermocouple, linearization,
external comparison
2#1110 B
N
E
R
S
J
L
T
K
U
C
TxK/XK(L)
2#0000
2#0001
2#0010
2#0011
2#0100
2#0101
2#0110
2#0111
2#1000
2#1001
2#1010
2#1011