Technical data
PAC1020
Equipment Manual, 05/2020, L1V30610008B-01
69
Connection components: Current connection, voltage connection
Connection components: Current connection, voltage connection
Conductor cross-section for copper
cable (Cu)
Rigid
0.25 ... 6 mm
2
(AWG 24 … 10)
Flexible
0.25 ... 6 mm
2
(AWG 24 … 10)
Flexible with end sleeve, without plastic
sleeve
0.25 … 4 mm
2
(AWG 24 … 12)
Flexible with end sleeve and plastic
sleeve
0.25 … 4 mm
2
(AWG 24 … 12)
2 conductors with the same cross-
section
(only for voltage connections)
Rigid
0.25 … 1.5 mm
2
(AWG 24 … 16)
Flexible
0.25 … 1.5 mm
2
(AWG 24 … 16)
Flexible with end sleeve, without plastic
sleeve
0.25 … 2.5 mm
2
(AWG 24 … 14)
Flexible with TWIN end sleeve and plas-
tic sleeve
0.25 … 2.5 mm
2
(AWG 24 … 14)
Tightening torque
0.85 Nm