3. Connect the wires to the connection terminals "+" and "-", observing the polarity and the
torques.
Use wires with a diameter of 0.5 ... 2.5 mm
2
.
If you use stranded wire used, you need a ferrule.
4. Apply the shield to the screw of the ground terminal .
The screw of the ground terminal is electrically connected to the external protective
conductor connection.
NOTICE
Incorrect measured values with incorrect grounding
The device must not be grounded using the "+" connection. It may otherwise malfunction
and be permanently damaged.
If necessary, ground the device using the "-" connection.
See also
Torques (Page 101)
5.2.3 Closing the device
Procedure
Cover over buttons Blanking plug
Cable gland Safety catch (front)
Safety catch (back) Cover (front), optionally with inspection window
Cover (rear) for electrical terminal compartment
Figure 5-4 View of the pressure transmitter: Left: Back right: Front view
Connecting
5.2 Connecting the device
SITRANS P320/P420 with 4 to 20 mA/HART
Compact Operating Instructions, 09/2018, A5E38874562-AB 41