$SSHQGL[6-
9

&*&
Annunciations 7SJ511 for LSA (DIN 19244 and according VDEW/ZVEI)
²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²
FNo. - Function number of annunciation
Op/Ft - Operation/Fault annunciation
C/CG: Coming/Coming and Going annunciation
V : Annunciation with Value
M : Measurand
LSA No.- Number of annunciation for former LSA (DIN 19244)
according to VDEW/ZVEI:
CA - Compatible Annunciation
GI - Annunciation for General Interrogation
BT - Binary Trace for fault recordings
Typ - Function type (p: according to the configured "Function type")
Inf - Information number
¿©©©©§©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©§©©©©©§©©©§©©©©©©©©©©©©©©©©¤
Ann.LSA VDEW/ZVEI
FNo. Meaning OpFtNo.CAGIBTTypInf
¨©©©©ª©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©ª©©ª©©ª©©©ª©©ª©©ª©©ª©©©ª©©©
11>User defined annunciation 1 CG 24CAGIBT p 27
12>User defined annunciation 2 CG 25CAGIBT p 28
13>User defined annunciation 3 CG 26CAGIBT p 29
14>User defined annunciation 4 CG 27CAGIBT p 30
51Device operative / healthy CG 1 GI 135 81
52Any protection operative CG CAGI p 18
55Re-start of processor system C 8CAp4
56Initial start of processor system C CAp5
59Real time response to LSA C 6
60LED Reset C 13CAp19
 
62Test mode CG CAGI p 21
63PC operation via system interface CG 135 83
95Parameters are being set CG 11CAGI p 22
96Parameter set A is active CG CAGI p 23
97Parameter set B is active CG CAGI p 24
98Parameter set C is active CG CAGI p 25
99Parameter set D is active CG CAGI p 26
110Annunciations lost (buffer overflow) C 9 135130
112Annunciations for LSA lost C 10 135131
113Fault tag lost BT135136
140General internal failure of device CG CAGI p 47
143Failure of internal 15 VDC power supplyCG 97 GI 135163
144Failure of internal 5 VDC power supply CG 98 GI 135164
145Failure of internal 0 VDC power supply CG 99 GI 135165
154Failure in the RKA module CG 100CAGI p 36
160Common alarm CG CAGI p 46
161Measured value supervision of currents CG CAGI p 32
162Failure: Current summation supervision CG 104 GI 135182
163Failure: Current symmetry supervision CG 107 GI 135183
204Fault recording initiated via bin.input BT135204
205Fault recording initiated via keyboard BT135205
206Fault recording initiated via PC interf BT135206
301Fault in the power system CG 2 135231
302Flt. event w. consecutive no. C 135232
 
501General fault detection of device CG142 BT150151
502General drop-off of device C 252 150152
511General trip of device C 143 BT150161
521Interrupted current: Phase L1(I/In) V249 150171
522Interrupted current: Phase L2(I/In) V250 150172
¥©©©©¦©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©¦©©¦©©¦©©©¦©©¦©©¦©©¦©©©¦©©©¾