Siemens AGM60.4A9 - QRB4 Yellow Flame Detection

Siemens AGM60.4A9
30 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
25/30
Smart Infrastructure CC1N7544en
21.05.2021
Technical Data (cont´d)
Open-circuit voltage at terminal QRB4
(X10
-
05 pin 3)
Approx. 5 V DC
Permissible length of QRB4 detector
cable (laid separately)
3 m (wire to wire 100 pF/m)
Threshold values when flame is supervised by QRB4
Start prevention (extraneous light)
Flame intensity (parameter 954)
10%
Operation
Flame intensity (parameter 954) >16%
Note!
In the case of the QRB4, the maximum intensity display is limited to approximately
40% due to the system (parameter 954).
Note!
Connection of QRB4 cables!
Blue cable of QRB4 to terminal X10-05 pin 4.
Black cable of QRB4 to terminal X10-05 pin 3.
Otherwise, the
QRB4 will not work.
Flame supervision with
QRB4