26/30
Smart Infrastructure CC1N7544en
21.05.2021
Technical Data (cont´d)
<5 W (typically) (without
Safety class I with parts according to II and III to
Galvanic separation between mains
voltage terminals and actuator signal lines
and actuator supply lines
No
Degree of protection IP00 according to EN 60529:1991 +
A1:2000 + A2:2013
Note:
The burner or boiler manufacturer (OEM)
must ensure degree of protection IP40 to
EN 60529:1991 + A1:2000 + A2:2013 for
burner controls by adequate installation of
The AGM60 together with the LMV36 is
suited for installation under the burner
hood or inside a control cabinet or control
Detection time fuel changeover
Switching frequency fuel changeove
Switching cycles fuel changeover
Permissible primary fuse (Si) (external) Max. 6.3 AT
Power must always be supplied via the
Caution!
Risk of damage to the switching contacts!
If the external primary fuse (Si) is blown due to overload or short-circuit at the
Mains supply:
Input current depending on the op
erating state of the LMV36
Mains voltage is monitored by the burner control
Mounting Top hat rail to DIN EN 60715,
Status input: Fuel selection, pressure switch
Input currents and input voltages
- UeMax
- UeMin
- IeMax
UN +10%
UN -15%
1.5 mA peak
Contact material recommendation for
external switching contact,
transducer (pressure switch-max,
Gold-plated silver contacts
Transition / settling behavior / bounce
- Perm. bounce time of contacts
Max. 50 ms (after the bounce time, the
contact must stay closed or open)
Voltage detection
- On
AC 90...132 V
Dual fuel switch unit