Smart Infrastructure CC1N7544en
21.05.2021
Technical Data (cont´d)
Mains voltage
AC 120 V
-
15% / +10%
Mains frequency
50/60 Hz
±
6%
Power co
nsumption
<5 W (typically) (without
actuator supply)
Safety class I with parts according to II and III to
EN 60730
-
1
:
2
0
1
6
Galvanic separation between mains
voltage terminals and actuator signal lines
and actuator supply lines
No
Degree of protection IP00 according to EN 60529:1991 +
A1:2000 + A2:2013
Note:
The burner or boiler manufacturer (OEM)
must ensure degree of protection IP40 to
EN 60529:1991 + A1:2000 + A2:2013 for
burner controls by adequate installation of
the AGM60...
The AGM60 together with the LMV36 is
suited for installation under the burner
hood or inside a control cabinet or control
panel
Detection time fuel changeover
<400 ms
Switching frequency fuel changeove
r
Min. 3 s
Switching cycles fuel changeover
Max. 5´000
Permissible primary fuse (Si) (external) Max. 6.3 AT
Power must always be supplied via the
LMV36
(refer to chapter
I
nputs / Outputs
)
Caution!
Risk of damage to the switching contacts!
If the external primary fuse (Si) is blown due to overload or short-circuit at the
terminals, the
AGM60
must be replaced.
Mains supply:
Input current depending on the op
erating state of the LMV36
Mains voltage is monitored by the burner control
Dimensions (W x H x D)
180.7 x 120.7 x 51.7 mm
Mounting Top hat rail to DIN EN 60715,
35 mm or screwed
Status input: Fuel selection, pressure switch
Input currents and input voltages
- UeMax
- UeMin
- IeMax
-
IeMin
UN +10%
UN -15%
1.5 mA peak
0.7 mA peak
Contact material recommendation for
external switching contact,
transducer (pressure switch-max,
POC)
Gold-plated silver contacts
Transition / settling behavior / bounce
- Perm. bounce time of contacts
when switching on/off
Max. 50 ms (after the bounce time, the
contact must stay closed or open)
UN
AC
120 V
Voltage detection
- On
-
Off
AC 90...132 V
<AC 40 V
Dual fuel switch unit
AGM60
Termin
al output
I
n
puts