Technical Data (cont´d)
Total contact output:
Rated voltage
AC 120 V, 50/60 Hz
Refer also
Total contact output
in chapter
Terminal output Outputs
Individual contact
loads:
Fuel valve
Rated
voltage
AC 120 V, 50/60 Hz
Rated current
1.6 pilot duty output dec
laration to UL732
Power factor
Cos >0.4
Safety valve (magnetic clutch / oil pump)
Rated voltage
AC 120 V, 50/60 Hz
Rated current 1.6 A pilot duty output declaration to
UL732
Power fac
tor
Cos >0.4
Connections for pressure switch
Rated voltage
AC 1
20 V , 50/60 Hz
Rated current
1.5 mA
Power factor
---
Power supply for pressure switch
-
max / POC (X5
-
02
pin
3 or X22
-
02
pin
3)
IaMax
<10 mA
Fuel feedback to LMV36.
.. (X31
-
02
pin
1 or X31
-
02
pin
2)
Ia
Max
<10 mA
Mains line LMV36 AGM60
Max. 3 m
(100 pF/m)
Fuel valves
Max. 3 m (100 pF/m)
Other lines
Max. 3 m (100 pF/m)
Fuel selector
Max. 20 m (100 pF/m)
Load controller
Max. 20 m (100 pF/m)
Specifi
cation as per
EN 60730-1:2016
Type of shutdown or interruption of each circuit
Shutdown with microswitch
Single
-
pole
Mode of operation
Type 2 B
The cross-sectional areas of the power supply lines (L, N and PE) must be capable of
carrying the rated currents according to the built-in unit fuse of the respective LMV36
(max. 6.3 AT).
Cross-sectional area Min. 0.75 mm² (single- or multi-core to
VDE 0100)
Cable insulations must satisfy the relevant temperature requirements and
environmental conditions.
The fixed connected actuator cables must not be extended.
Terminal
output
Ou
t
puts
Cable lengths
Cross
-
sectional areas
Electrical connections of
actuators