5
Fire & Security Products
Siemens Building Technologies Group 06.2001
Note: all values are approximative !
Smoke sensitivity: To simplify the comparison of smoke sensitivities between the
parameter sets, we are specifying an AlgoRex smoke sensitivity index for danger level 3.
Please note, that this index is a relative figure, where 2 means an increased sensitivity by
a factor of 2 (compared to the parameter set with index 1); therefore the detector will alarm
at half the smoke density if measured in the CEN smoke tunnel acc. to EN54.
An AlgoRex smoke sens. Index of 0 means no alarm with smoke only.
Important: The parameter sets APS083S, APS084S and APS080SH must only be ap-
plied for special applications!
APS080: Caution, low security against false alarm! Parameter set with very high sensitivity
and extreme fast reaction time.
APS083: In mode present, detection of smoke without temperature rise will not lead to a
danger level 3. This behaviour is outside the standard EN547; in mode absent, EN547
is fulfilled.
APS084: This parameter set prevents nuisance alarms due to short and single nuisance
signals. Long or multiple events may lead to danger level 3.
1)
The detector DOT1151-Ex with APS080SH can have a slightly lower electromagnetic
compatibility (APS081S passed EMC tests in the meantime).
2)
Not available for temporary change of detector parameter set on CT/CI due to further
risks in application.
3)
IMPORTANT NOTE regarding APS083 and APS084 (see info MI290):
Unfortunately there has been a mistaken parameter value in detector DOT1151A Index
ke; however, this mistake only affects behaviour in parameter sets 083/084. As a result,
the detector may not be able to go into alarm on reasonable smoke density!
--> You must never choose APS083 or APS084 with a detector DOT1151A with Index ke!
As a simple rule of thumb, only use APS083 or APS084 with detectors DOT115x with
Technical Index ”_f” or later.
Detectors DOT1151A-Ex are not concerned by this fault.
The Index is shown on the detector label as two letters following the part number (e.g.
DOT1151A: P/N 486695 ke); first letter means Schematic Index, second letter means
Technical Index. Both are in alphabetical order.