Air sampling smoke detection system
AD2-C11 rev.d
Quick Guide for Commissioning
1 Installation
§ Connect power (24VDC)
§ Connect the detector lines
§ Connect reset input (if S3 = ON)
§ Install the detector bases and the smoke detectors
§ Prepare for operation with 1 or 2 pipe systems
§ Connect pipe system or test pipe
2 Set Up
Set DIP switches S2 on pcb E596 according to tables below:
Air flow monitoring
Switch S2 delay time Switch S2 Range
A(1) B(2) C(3) D(4)
OFF
ON
short 30 s
ON
OFF small I
ON
OFF middle 2 min. (standard) OFF
ON
middle II
ON ON
long 15 min.
OFF OFF large III (standard)
OFF OFF very long 1 h
ON ON
very large IV
Fault
Switch S3
OFF Fault not latching (standard)
ON
Fault latching until reset
Atmospheric pressure compensation
R28 MP1 (+) MP2 (-) see correction table for atm.pressure or 2,50 V (standard)
3 Commissioning
Initializing of airflow monitoring
1. press button S1 “Init several times:
for 1 tube system:
for 2 tube systems:
green LED and yellow LED left flashes
green LED und yellow LEDs left and right flashes
2. Fix cover and tighten screws within the next 2 min.
3. Initialization active ca. 20 min., green and yellow LED flashing
4. Unit ready green LED on
Fire & Security Products
Siemens Building Technologies Group

Other manuals for Siemens AD2-C11

Question and Answer IconNeed help?

Do you have a question about the Siemens AD2-C11 and is the answer not in the manual?

Siemens AD2-C11 Specifications

General IconGeneral
BrandSiemens
ModelAD2-C11
CategorySmoke Alarm
LanguageEnglish

Summary

Installation

Set Up

Air Flow Monitoring Settings

Configuration of DIP switches for air flow monitoring delay time and range.

Fault Handling Setup

Setting the behavior of the fault signal latching mechanism via DIP switch S3.

Atmospheric Pressure Compensation

Configuration for atmospheric pressure compensation using MP1 and MP2 inputs.

Commissioning

Initializing Airflow Monitoring

Procedure for initializing airflow monitoring using button S1 and observing LED indicators.

Related product manuals