EasyManua.ls Logo

Siemens DI-3 - User Manual

Siemens DI-3
4 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
These instructions are written in accordance with the
installation guidelines of NFPA 72, National Fire Alarm
Code, and CAN/ULC-S524, The Installation of Fire Alarm
Systems.
DETECTOR PLACEMENT
Although no specific spacings have been allocated for the
detectors used for the 0 to 300 ft/min clean air velocity
application, use 30 foot center spacing (900 sq ft) from NFPA
Standard 72 Chapter 5 and CAN/ULC-S524, if practical, as a
guide or starting point for a detector installation layout. This
spacing, however, is based on ideal conditions — smooth
ceiling, no air movement, and no physical obstructions. In
some applications, therefore, considerably less area is
protected adequately by each smoke detector. This is why it
is mandatory to closely follow the installation drawings. In all
installations (except in special circumstances, such as in
computer room underfloors where the velocity may be
between 300 and 1200 ft/min) the detector should be located
on the ceiling, a minimum of 6 inches from a side wall, or on
a wall, 6 inches from the ceiling.
Should questions arise regarding detector placement,
drawings provided or approved by Siemens Industry, Inc., or
by its authorized distributors should be followed. This is
extremely important! The detector placements shown on
these drawings have been chosen after a careful evaluation
To initiating circuit of
compatible control
unit (See †NOTE and
Compatibility Chart)
P/N 315-081882, Rev. 2
Connection for listed remote lamp
RL-30 or equivalent, audible base
ADB-3, or relay RR-3, 40mA max, at
24V (one per detector.) CAUTION: Only
one critical function remote should be
used in each circuit, since only one alarm
per circuit is guaranteed.
NOTE: The Models DI-3, DI-3H, DI-3IS*, DI-A3, and
DI-A3H are rated at 16-25.7 VDC—3 volt peak to
peak maximum ripple. Supervisory current 110μA
max steady state. 350μA peak surge upon
application of power, and 135mA max in alarm.
Figure 1 SIEMENS Models DI-3, DI-3H, DI-3IS, DI-A3, AND DI-A3H
Installation And Wiring Diagram
*NOTE: The DI-3IS is FM listed only. Do not use remote function with the DI-3IS.
Installation/Wiring Instructions
Smoke and Fire Detector Models DI-3, DI-3H, DI-3IS*, DI-A3, and DI-A3H
End-of-line
device
observe
polarity
if applicable
Siemens Industry, Inc.
Building Technologies Division
P/N 315-081943-19
of all facets of the area being protected. Such factors as air
currents, temperature, humidity, pressure, and the nature of
the load have been carefully considered. Especially noted have
been the room or area configuration and the type of ceiling
(sloped or flat, smooth or beamed). Siemens Industry, Inc.'s
extensive experience in the design of the system assures the
optimum detector placement and is reflected in these drawings.
Sound engineering judgment by qualified personnel must
prevail.
TO AVOID NUISANCE ALARMS:
DO NOT locate the DI-3, DI-3H, or DI-3IS detectors where
excessive smoke concentrations exist under normal conditions
or in areas of prolonged high relative humidity where
condensation will occur.
DO NOT locate the DI-3, DI-3H, or DI-3IS detectors adjacent
to an oil burner, kitchen, or garage where exhaust fumes could
trigger an alarm. Other causes of false alarms are dust
accumulation, high wind velocity, heavy concentrations of
steam, heavy pipe or cigar smoke, and certain aerosol sprays.
DO NOT locate the DI-A3 or DI-A3H detectors in an area of
prolonged high relative humidity when condensation will occur
or adjacent to oil burners or in garages, where exhaust fumes
could trigger an alarm.
Question and Answer IconNeed help?

Do you have a question about the Siemens DI-3 and is the answer not in the manual?

Summary

Detector Placement

Detector Spacing Guidelines

Use 30-foot spacing as a guide, considering ideal conditions and specific applications.

Nuisance Alarm Prevention

Avoid locations with high humidity, dust, steam, or exhaust fumes to prevent false alarms.

Air Currents

Airflow Impact on Smoke Travel

Consider air currents from diffusers, windows, and doors affecting smoke detection.

Ceiling Height Considerations

Account for ceiling height, especially in large spaces, for smoke travel distance.

Special Ceiling Construction Factors

Obstruction Impact on Airflow

Account for beams, joists, and ducts that may alter smoke and air movement.

Temperature and Humidity

Operating Environment Limits

Detectors operate between 0-37.8°C and up to 93% humidity (non-condensing).

Pressure

Altitude Effects on Sensitivity

Lower air pressure at higher altitudes may affect ionization detector sensitivity.

Applications

Model Specific Applications

Details on model suitability for open areas, computer facilities, and air ducts based on velocity and altitude.

Special Note - High Stockpiling

Spacing for High Stockpiling

Requires closer spacing and tiered locations based on stock, height, and judgment.

DI-3 IS Only

Hazardous Atmosphere Use

DI-3IS is for Class I, Division 1 areas; requires specific barriers or isolators.

Detector Wiring

Interconnection and Control Panels

Detectors connect per diagrams; follow panel wiring instructions and check detector limits.

Detector Mounting

Base Installation and Wiring

Route wires, position LED mark, mount base, and make terminal connections.

Loop Continuity Check

Ensure loop continuity after base installation, using a jumper for testing.

Detector Head Installation

Aligning and Securing Head

Align notch, push head into base, and twist clockwise to engage connections.

Removing Detector Head

Push head up and rotate counterclockwise to disengage from the base.

Detector Sensitivity

Sensitivity Adjustment

Field adjustable for DI-3/DI-3H/DI-3IS; adjust towards '+' for increased sensitivity.

Factory Set Sensitivity

DI-A3 and DI-A3H detectors have factory-set sensitivity and are not field adjustable.

Testing

Sensitivity Test Procedure

Use Model TM-13 tester via sensitivity jack for testing within factory limits.

Go;No Go Test Gas

Use SIEMENS Test Gas P/N 315-282747 for GO/NO GO operation testing.

Maintenance

Cleaning Detectors

Gently brush or vacuum slots; disconnect power before cleaning if using suction.

Sensitivity Adjustment and Replacement

Adjust sensitivity; replace head if outside limits. Do not disassemble detectors.

Compatible Control Equipment

Non-Intrinsically Safe Models

Lists compatible control equipment for DI-3, DI-3H, DI-A3, and DI-A3H models.

Intrinsically Safe Model DI-3 IS

Lists compatible control equipment for DI-3IS FM Approved model.

Overview

This document provides installation and wiring instructions for Siemens Smoke and Fire Detector Models DI-3, DI-3H, DI-3IS*, DI-A3, and DI-A3H. These instructions adhere to the installation guidelines of NFPA 72, National Fire Alarm Code, and CAN/ULC-S524, The Installation of Fire Alarm Systems.

Function Description

These detectors are designed to sense smoke and fire conditions within a protected area. They integrate into a compatible control unit to provide early warning of potential fire events. The DI-3IS model is specifically FM approved for intrinsically safe applications.

Important Technical Specifications

  • Voltage Rating: Models DI-3, DI-3H, DI-3IS*, DI-A3, and DI-A3H are rated at 16-25.7 VDC with a 3-volt peak-to-peak maximum ripple.
  • Supervisory Current: 110µA maximum steady state.
  • Surge Current: 350µA peak surge upon application of power.
  • Alarm Current: 135mA maximum in alarm.
  • Remote Functions: Connections are available for listed remote lamps (RL-30 or equivalent), audible bases (ADB-3), or relays (RR-3), with a maximum draw of 40mA at 24V. CAUTION: Only one critical function remote should be used per circuit, as only one alarm per circuit is guaranteed.
  • DI-3IS Restriction: The DI-3IS model is FM listed only and should not use remote functions.
  • Temperature and Humidity Range:
    • DI-3, DI-3H, DI-3IS, DI-A3, and DI-A3H: 32°F (0°C) to 100°F (37.8°C).
    • DI-A3 and DI-A3H: 32°F (0°C) to 105°F (40.6°C).
    • All models can be used in environments where the humidity does not exceed 93% (non-condensing).

Usage Features

Detector Placement: While no specific spacings are allocated for these detectors in clean air velocity applications (0 to 300 ft/min), a 30-foot center spacing (900 sq ft) from NFPA Standard 72 Chapter 5 and CAN/ULC-S524 is a practical guide. However, actual protected area may be less due to ideal conditions not always being met (e.g., smooth ceiling, no air movement, physical obstructions). It is crucial to follow installation drawings provided or approved by Siemens Industry, Inc. Detectors should be located on the ceiling, a minimum of 6 inches from a side wall, or on a wall, 6 inches from the ceiling, except in special circumstances like computer room underfloors where velocity may be between 300 and 1200 ft/min.

Special Ceiling Construction Factors: Ceiling obstructions significantly impact smoke and fire product movement. Obstructions like beams, joists, and ducts can create "dead air" spaces or channel smoke, affecting detector placement. For detailed guidance, refer to the Initiating Devices chapter of NFPA Standard 72 for specific construction types (e.g., beam, suspended, level, sloped, and peaked ceilings).

Air Currents: Air movement significantly influences how smoke and fire products travel. Detectors should be placed to intercept these products before they dissipate. Consideration must be given to windows, doors, and HVAC systems. Detectors should not be installed in the air stream of a room air supply diffuser if it may advantageously position the detector closer to an air return.

Pressure: Normal changes in atmospheric pressure have a negligible effect on detector sensitivity. However, lower air pressure at higher altitudes does have some effect on the sensitivity of ionization type detectors.

To Avoid Nuisance Alarms:

  • DI-3, DI-3H, DI-3IS: Do not locate where excessive smoke concentrations exist under normal conditions, in areas of prolonged high relative humidity causing condensation, or adjacent to oil burners, kitchens, or garages where exhaust fumes could trigger an alarm. Other causes include dust accumulation, high wind velocity, heavy steam concentrations, heavy pipe or cigar smoke, and certain aerosol sprays.
  • DI-A3, DI-A3H: Do not locate in areas of prolonged high relative humidity causing condensation, or adjacent to oil burners or in garages where exhaust fumes could trigger an alarm.

Detector Wiring: Siemens Industry, Inc. detectors are interconnected as shown in Figure 1. Wiring should be done according to the Wiring Connection drawing, the control panel manual, and the installation manual. Ensure proper documentation and adherence to the maximum number of detectors permitted per circuit.

Detector Mounting: The detector is provided with a separate base which attaches to a standard 4-inch square, 4-inch octagonal, or single gang electrical box. The depth of the box is determined by the National Electrical Code for the number and size of the conductors used.

  • Route all wires outward from the outlet box.
  • When the alarm LED wiring is critical, position the LED mark in the base in the intended direction (See Figure 2).
  • Mount base to outlet box and route wires through the hole in the center of the base.
  • Make connections directly to the base terminals, referring to Figure 1 for details.
  • After all bases are installed, including the end-of-line device, check loop continuity. Refer to system operation manual for procedure. If continuity is acceptable, remove jumper at each detector location and proceed with detector head installation.

Installation of Detector Head:

  1. Align notch in detector cover to raised surface on outer ring of base (See Figure 3).
  2. Push detector head into base and rotate clockwise to engage electrical connections. The detector will automatically stop and lock into place.
  3. To remove, push detector head up into the base while rotating the detector head counterclockwise. Continue to rotate counterclockwise until stop is reached. Then pull downward to disengage from base.

Detector Sensitivity: The normal sensitivity range is found on the back of the detector. A decrease in sensitivity indicates the detector needs cleaning, ambient conditions have changed, or the detector is faulty.

  • DI-3, DI-3H, DI-3IS: Sensitivity is field adjustable via a potentiometer on the detector head face (See Figure 4). Adjustment towards "+" increases sensitivity; adjustment towards "-" decreases sensitivity. The adjustment range is ± 0.50 VDC of the nominal factory setting.
  • DI-A3, DI-A3H: Sensitivity is factory set and not field adjustable.

Testing: Testing should be performed by qualified personnel. Use a sensitivity jack test to directly measure detector sensitivity in its mounted position while powered by the system. Access the sensitivity test jack through five holes on the front face of the detector (See Figure 4). Use sensitivity tester Model TM-13 (P/N 315-086641). Test frequency should be in accordance with NFPA Standard 72. For GO/NO GO operation, use Siemens Test Gas, P/N 315-282747, following label instructions.

Maintenance Features

Cleaning: Dust accumulation can shift detector sensitivity. Periodic checks and light cleaning are necessary. The minimum test schedule can be found in NFPA 72, Chapter 7 (U.S.) and CAN/ULC-S537 (Canada). Cleaning intervals should be tailored to the individual detector environment. Clean by lightly brushing all open slots. Vacuum cleaning is also possible, but power should be disconnected to prevent alarms.

Repair: Detectors are not designed for thorough cleaning in the field. If sensitivity falls outside acceptable limits and cannot be adjusted back (where applicable), replace the detector head. Send removed heads to the nearest Siemens Industry, Inc. Authorized Service Center for servicing. CAUTION: Under no circumstances should the detector head be disassembled. No field repairs should be attempted. Detectors are factory repairable only.

Siemens DI-3 Specifications

General IconGeneral
BrandSiemens
ModelDI-3
CategorySmoke Alarm
LanguageEnglish

Related product manuals