Siemens room unit QAA822 Building Technologies
Number
Parameter description
001
KNX communication
Communication is functioning -OK
Communication is not functioning -NG
002
Individual address - (X.1.1)
The range is 0 to 15. The preset value is 0.
003
Individual address - (1.X.1)
The range is 0 to 15. The preset value is 1.
004
Individual address - (1.1.X)
The range is 1 to 252. The preset value is 1.
005
Byte address - (X.1.1)
The range is 1 to 126. The preset value is 5.
006
Room address (1.X.1)
The range is 1 to 14. The preset value is 1.
007
Zone address - (1.1.X)
The range is 1 to 15. The preset value is 1.
008
Enable the network failure detection
Enables or disables the detection of the
communication network failure. The failure is
indicated by a blinking notice “NET”.
009
Automatic assignment of the individual
address
0 the room unit uses the defined fixed individual
address.
1 the room unit generates automatically the
individual addresses.
Note
*)
The configuration parameters are set on the control panel of the
Climatix controller or through the web viewer of the computer
connected to the Climatix controller in the OS-designated
switchboard. The parameter setting is described in the document
Detailed instructions for control through HMI Climatix“.