CPUs
1-55
PLC S7-300, CPU Specifications CPU 312 IFM to CPU 318-2 DP
A5E00111190-01
Technical Specifications of the Digital Outputs of the CPU 314IFM
Remarks
When the supply voltage is switched on a pulse occurs on the digital outputs! This
can be 50 ms long within the permissible output current range. You must not,
therefore, use the digital outputs to trigger high-speed counters.
Module-Specific Data
Number of outputs 16
Cable length
Unshielded
Shielded
max. 600 m
max. 1000 m
Voltages, Currents, Potentials
Rated load current L+
Polarity reversal
protection
24V DC
No
Total current of outputs (per
group)
(horizontal
configuration)
up to 40°C
up to 60°C
(vertical configuration)
up to 40°C
max. 4 A
max. 2 A
max. 2 A
Galvanic isolation
between channels and
backplane bus
Between the channels
in groups of
Yes
Yes
8
Permissible potential
difference
Between different
circuits
75V DC
60V AC
Insulation tested at 500V DC
Current consumption
on L+ supply (no load) max. 100 mA
Status, Interrupts; Diagnostics
Status display 1 green LED per
channel
Interrupts None
Diagnostic functions None
Actuator Selection Data
Output voltage
For 1 signal min. L+ (-0.8 V)
Output current
For 1 signal
Rated value
Permissible range
For 0 signal
(residual current)
0.5 A
5 mA to 0.6 A
max. 0.5 mA
Load impedance range 48 to 4 k
Lamp load max. 5 W
Parallel connection of 2
outputs
For dual-channel
triggering of a load
For performance
increase
Possible, only
outputs of the same
group
Not possible
Triggering of a digital input Possible
Switching frequency
For resistive load
For inductive load to
IEC947-5-1, DC 13
For lamp load
max. 100 Hz
max. 0.5 Hz
max. 100 Hz
Inductive breaking voltage
limited internally to
typical L+ (- 48 V)
Short-circuit protection of
the output
Response threshold
yes, electronically
timed
typical 1a