CPUs
1-54
PLC S7-300, CPU Specifications CPU 312 IFM to CPU 318-2 DP
A5E00111190-01
Technical Specifications of the Digital Inputs of the CPU 314IFM
Module-Specific Data
Number of inputs 16
Cable length
Unshielded
Shielded
max. 600 m
max. 1000 m
Voltages, Currents, Potentials
Rated load current L+
Polarity reversal
protection
24V DC
Yes
Number of inputs that can
be triggered simultaneously
(horizontal
configuration)
up to 60°C
(vertical configuration)
up to 40°C
16
16
16
Galvanic isolation
between channels and
backplane bus
Yes
Permissible potential
difference
Between different
circuits
75V DC
60V AC
Insulation tested at 500V DC
Current consumption
on power supply L+ max. 40 mA
Status, Interrupts; Diagnostics
Status display 1 green LED per
channel
Interrupts None
Diagnostic functions None
Sensor Selection Data
Input voltage
Rated value
For 1 signal
For 0 signal
24V DC
11 to 30 V
-3 to 5 V
Input current
For 1 signal typical 7 mA
Input delay time
For 0 to 1
For 1 to 0
1.2 to 4.8 ms
1.2 to 4.8 ms
Input characteristic to IEC 1131, Type 2
Connection of 2-wire
BEROs
Permissible quiescent
current
Possible
max. 2 mA