Expansion up to a complex fire detection system
The structure of the C-Bus network permits the connection of several control panels
and control terminals. These stations can be mounted in the same housing or in sepa-
rate housings. The location is chosen according to where it is easiest for operation or
installation.
However, the fire detection system can be extended even further. Several C-Bus net-
works can be combined to a danger management system by means of a gateway
CK11.
Control unit CI11
A max. of 16 stations can be freely combined
on a single C-Bus
- up to 15 CC11 control units
- up to 15 CT11 control terminals
- up to 16 CI11 control units
- up to 15 CK11 gateways
C-Bus
CPU
Gateway
CK11
Control unit CC11
Control terminal
CT11
CERBAN/CERLOOP
Danger management system
(DMS/LMS)
Gateway
CK11
further C-Bus network
C-Bus
CPU
Stations
CI11
CC11
Max. number of detectors
> 500
> 2000
Number of line and control
modules
up to 8 up to 16
Control terminal
permanently built-in
built-in or mounted in separate housing
Metal housing, type
H38G220
H38G320
H47...
H67...
H98...
Dimensions W x H x D [mm]
515 x 602 x 100
515 x 602 x 155
434 x 735 x 300
434 x 1130 x 300
600 x 2015 x 300
5
Building Technologies
CPS Fire Safety 04.2014