EasyManua.ls Logo

Siemens CS1140 - Technical Data; Control Units Specifications; Environmental Conditions; Approvals

Siemens CS1140
8 pages
Print Icon
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
Control units
CI11 / CC11
Mains supply voltage
AC 115/230 V, +10 %/-15 %, 50/60 Hz
Power consumption
40...220 VA
Emergency power operating
– Standard
– optional
12…24 h
…72 h
Protection category (IEC 60529)
– Housing H38
– Housings H47 / H67 / H98
IP40
IP30
Color
– Housings
– Front surface (control console)
light grey, RAL 7035
silver, RAL 9006 / grey Pantone 427C, 431C
Operating temperature
0…+55 °C (B3Q661)
0…+40 °C (B3Q681/686)
Storage temperature
−20…+60 °C
Humidity (no condensation)
– at T = 25 ±3 °C
– at T = 40 ±2 °C
≥95 % rel.
93 % rel.
Approvals
– VdS
– LPCB
– others
G294042
126bk/01
on request
Bus / Detection line FD20
Sinteso
TM
Interactive
DS1150
AnalogPLUS
DS1130
Collective
DS1100
Number of addresses
…126
…128
…128
1
Number of wires
2
2
2
2
Network structure
Master/Slave
Master/Slave
Master/Slave
no
Loop line
yes
yes
yes
no
Short circuit proof
yes
yes
yes
no
T-tap
yes
yes
no
no
Siemens Switzerland Ltd
Infrastructure & Cities Sector
Building Technologies Division
International Headquarters
CPS Fire Safety
Gubelstrasse 22
CH-6301 Zug
Tel. +41 41 - 724 24 24
www.siemens.com/buildingtechnologies
© 2014 Copyright by Siemens Schweiz AG
Technical specifications and availability subject to change without notice.
Document no. 008722_c_en_-- Manual S11
Edition 04.2014 Section 7