Siemens Desigo Touch and Web CM111029en_04
Building Technologies Compatibility & limitations – System limits 2014-08-15
2.5.2.4 Connected web clients
Item Limits Description
Touch panel 10* Max. number of touch panels per PXG3.W100 with overview page.
Web clients, max. system
design
3* Max. number of registered users per PXG3.W100, where the limit of
permanently displayed BACnet objects of all clients may not be ex-
ceeded at maximum system design
1)
.
At low system design, more than 3 users can be logged in concurrent-
ly.
Example: 1 customized view at 3 graphics pages at 10 BACnet objects
each. If 10 web clients are connected to it, the system limit (300 per-
manently displayed BACnet objects) is reached.
All system limits must be adhered to simultaneously.
Limit* Technical limit, tested.
Limit Recommended limit, tested.
[Limit] Recommended limit, not tested.
· 20 customized views
· 5 graphics pages per customized view
· 20 BACnet objects per graphics page
ð 2000 BACnet objects total
ð 100 BACnet objects per customized view
· 3 Web clients with the above design
ð 300 permanently displayed BACnet objects
· 10 trends per customized view
· 10 schedulers per customized view
ð Important: The configuration data size < 7MB applies to all of the above
1)
Example for max.
system design
ð with system limits