EasyManua.ls Logo

Siemens Desigo Touch Series - Touch Panel Commissioning - Step-by-Step

Siemens Desigo Touch Series
22 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 / 22
Siemens Desigo Touch and Web CM111029en_04
Building Technologies Commissioning – Touch panel commissioning – Step-by-step 2014-08-15
1.4 Touch panel commissioning Step-by-step
1.4.1 About procedures
The following step-by-step procedures consider all actions, settings, etc. It is pos-
sible that, in the past, you may have applied and now wish to continue a different
procedure. The procedure described here merely shows the procedure identified
as best by development.
1.4.2 Procedure
1. If not yet done: Connect the Desigo touch panel to the corresponding network
plug using the network cable (RJ45).
2. If not yet done: Connect to power.
3. Wait for the touch panel to start.
---> This process may take a few seconds; the Language page is displayed.
4. Select the language.
---> 16 languages are integrated. English is the default language.
5. Save with Next.
---> The page “Network Settings – IPv4” opens.
Note
Two ways are available for the following step:
a. Automatically using DHCP (self-explanatory).
b. Manual via the alphanumeric keypad.
Below, we describe how to proceed with a manual entry. The procedure for IPv4 is
virtually automatic for the DHCP method.

Related product manuals