Standard I/O Modules
SICAM A8000 Series, SICAM I/O Modules Unrestricted 39
DC8-012-2.06, Edition 09.2019
2.5.3 Technical Data
Binary outputs
8 binary outputs
(relay)
• 4 groups, 2 outputs each, potential-free
• Galvanic insulation
Nominal voltages
•
DC 24/48/60/110/220 V
• AC 110/230 V
Maximum continuous current
Standard circuitry
Circuitry with derating at 5 A
Power augmentation
1)
• 8 outputs max. 3 A each (5 A/1 min)
• 2 outputs max. 5 A each
• 6 outputs max. 2 A each
or
• 4 output max. 5 A each
• 4 outputs max. 0 A each (relay must not be activated)
• 4 outputs max. 6 A each max. DC 24 V +20%
max. AC 230 V +10%
Switching capacity DC voltage
• Min. 50 mW at DC 5 V
• Max. acc. to diagram
AC voltage
• Max. 1250 VA 5 A / AC 250 V, resistive load
• Max. 500 VA 2 A / AC 250 V, cosϕ = 0.4
Switching cycles 3 • 10
4
Output circuits Max. DC 250 V / AC 253 V
The circuits are operated by means of an external voltage
UL/CUL DC 6 A / 24 V
AC 6 A / 253 V resistive
Pilot duty: R300, B300
Power Supply
Operating voltage DC 4.75…5.5 V 800 mW
The voltage is picked off at the system bus