Page EN-8 ST-H Transducer – QUICK START MANUAL A5E32105880
mmmmm
English
Mounting
Do not mount the transducer directly to metal. Use a plastic type coupling and nipple for
isolation (customer supplied).
Mount the transducer so that it is above the maximum material level by at least the
blanking value. Refer to the associated controller manual.
For liquid applications, the transducer must be mounted so that the axis of transmission is
perpendicular to the liquid surface. For tanks with a parabolic top, an Easy Aimer may be
used to mount the transducer face perpendicular to the liquid surface.
For solids applications, use a Siemens Milltronics Easy Aimer to aim the transducer.
Where the transducer is mounted to a standpipe, the inner standpipe surface and end
must be smooth and free of burrs, ridges, and seams.
Consider the optional temperature sensor when mounting the transducer.
Do not overtighten mounting. Hand tightening of the mounting hardware is sufficient.
Mounting – Solids Applications
Non-Corrosive Applications
WARNING!
NOT
suitable
for use in a
corrosive
environment.
In solids applications, mount the transducer so that it is aimed toward the low level draw point. Use
the optional Siemens Milltronics Easy Aimer to facilitate this mounting.
Easy Aimer
(typical model)
transducer