2
Building Technologies
CPS Fire Safety
System overview
Detector line Cerberus 110-series
Detector line Synova 600
Detector line AlgoRex DS110x
Detector line Cerberus 110-series
Synova 300
Call point line
Mixed line
(detector/call point with
differentiation)
Intrinsically safe detectors
EX-area
24V
Linear smoke detector
or flame detector
Monitored control lines for
- horns, sirens
- beacons
Fire controls
- internal relays
Remote transmission
- internal contact
max. 5
max. 1
max. 32
max. 32
DC1192
SB3
Detector line Cerberus 110-series
with line continuity
according to BS 5839 Pt1
Various panel types with different features
Types Zones Monitored
outputs
Relay
outputs
Output cards Power supply Battery
FC121-ZA 2 2 1 1 25 W Max. 7 Ah
FC122-ZA 4 2 1 1 25 W Max. 7 Ah
FC123-ZA 8 2 1 2 70 W Max. 17 Ah
FC124-ZA 12 2 1 3 70 W Max. 17 Ah
Functional elements
The FC121-ZA, FC122-ZA, FC123-ZA, FC124-ZA are compact fire control panels with
an integrated operating unit for 2 or 4 or 8 or 12 zones.
Processes signals from the 110-series / DS11 and SynoLINE300/600 series.
The control unit has been designed to be very simple to use while offering exceptional
flexibility via a comprehensive feature list.
– All detector lines are monitored for ground faults.
– Adaptation of the customer text directly on the panel via menu navigation.
– Up to 1000 events can be stored according to various criteria.
– Automatic summer/winter time change.
Detection
– Each line supports 110-series / DS11 and SynoLINE300/600 series devices
– Detectors and call points on same line with functional differentiation (where allowed)
– Intrinsically safe detectors via line coupler DC1192 and safety barrier SB3