Siemens Industry, Inc. A6V10337045_en--_n
Smart Infrastructure
DACT Alarm, Trouble Supervisory
Retransmission interval
Y
DACT retransmission intervals can be
configured up to 24 hours
be configured up to 6 hours
unlocking timing
Y
Fire Control can be user defined
accordingly
Fire control to be configured to
within 10 minutes “unlocking” after
loss of primary power
release operation timing
Y
Releasing Control Group can be user
defined accordingly
Releasing Control Group to be
configured to 60 secs. Max release
Interconnected/networked panel
loops pathway configuration Y
Interconnected/networked loops could
be configured Class X, A or B
Configuring Class X network loops
via the Redundancy management
configuration setting
Alarm verification restart time
Y
Alarm verification restart time user
defined
Max restart time shall not exceed 30
seconds when accomplished on a
multiple circuit (zone) or system
basis
Alarm verification configuration
N
Alarm verification devices in a cross
zone operation
Alarm verification shall not be used
in initiating device circuits intended
for cross-zone operations
Y
CO programming tone user defined
CO detector MUST be programmed
as Temporal 4
Y
Trouble supervision setting can be on
or off
reporting must be “on” and
activated
Y
Ground fault supervision for the power
supply can be activated or turned off
Ground fault supervision must be
“on” and activated
Signal Silence Inhibit Feature
Y
minutes