EasyManua.ls Logo

Siemens FC2025 - Page 7

Siemens FC2025
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7
Siemens Industry, Inc. A6V10337045_en--_n
Smart Infrastructure
Ability for MNS NACs to be
configured as
Silenceable
N
NACs dedicated for MNS application
can be configured as
Silenceable
Acceptable
-
NACs dedicat
ed for
MNS application must be configured
as
Non-Silenceable
.
BACnet client Supervision timeout
to delay reporting network
supervision.
Y
Ability for the BACnet supervision
timeout to be configured from 1s to 10
minutes.
Acceptable Range must be between
1 sec and 85 sec.
DACT Alarm, Trouble Supervisory
Retransmission interval
Y
DACT retransmission intervals can be
configured up to 24 hours
DACT retransmission intervals must
be configured up to 6 hours
Loss of primary power
-
Door
unlocking timing
Y
Fire Control can be user defined
accordingly
Fire control to be configured to
within 10 minutes “unlocking” after
loss of primary power
Releasing operation
Door
release operation timing
Y
Releasing Control Group can be user
defined accordingly
Releasing Control Group to be
configured to 60 secs. Max release
Interconnected/networked panel
loops pathway configuration Y
Interconnected/networked loops could
be configured Class X, A or B
Configuring Class X network loops
via the Redundancy management
configuration setting
Alarm verification restart time
Y
Alarm verification restart time user
defined
Max restart time shall not exceed 30
seconds when accomplished on a
multiple circuit (zone) or system
basis
Alarm verification configuration
N
Alarm verification devices in a cross
-
zone operation
Alarm verification shall not be used
in initiating device circuits intended
for cross-zone operations
CO
alarm tone p
rogramming
Y
CO programming tone user defined
CO detector MUST be programmed
as Temporal 4
PAD
-
5 Trouble supervision
Y
Trouble supervision setting can be on
or off
Error reporting must be “on” and
activated
PAD
-
5 Ground Fault monitoring
Y
Ground fault supervision for the power
supply can be activated or turned off
Ground fault
supervision must be
“on” and activated
Signal Silence Inhibit Feature
Y
Signal Silence Inhibit range 0
-
30
minutes
ULC minimum is 5 minutes

Other manuals for Siemens FC2025

Related product manuals