Siemens Industry, Inc
, A6V10334254_en--_g
Building Technologies Division
10
FCA2015-U1 EVENT CODES
Event Type
SIA DCS
(8 or 20)
*
5
Ademco
Contact ID
*
5
3/1
1400 Hz or
2300HZ
4/2
1400 Hz or
2300HZ
Fire Alarm
FA pppp
1 110 0p ppp
0
01
Fire Alarm Restore
(Through Reset)
FH pppp
3 110 0p ppp
2
21
Smoke Alarm
FA pppp
1 111 0p ppp
0
01
Smoke Alarm Restore
FH pppp
3 111 0p ppp
2 21
Heat Alarm
FA pppp
1 114 0p ppp
0
01
Heat Alarm Restore
FH pppp
3 114 0p ppp
2
21
Pull Station Alarm
FA pppp
1 115 0p ppp
0
01
Pull Station Alarm Restore
FH pppp
3 115 0p ppp
2
21
Waterflow Alarm
SA
pppp
1 113 0
p ppp
0
02
Waterflow Alarm Restore
SH pppp
3 113 0p ppp
2
22
Supervisory
SS pppp
1 200 0p ppp
6
66
Supervisory Restore
SR pppp
3 200 0p ppp
7
76
AC Trouble
AT
1 301 00 000
8
80
AC Trouble Restore
AR
3 301 00 000
7
70
Trouble
FT pppp
1 373 0p ppp
8
83
Trouble Restore
FJ pppp
3 373 0p ppp
7
73
System Battery Trouble
YT
1 302 00 000
8
87
System Battery Trouble Restore
YR
3 302 00 000
7
77
Phone Line 1 Trouble
LT 1
1 351 00 000
8
81
Phone Line 1 Trouble Restore
LR 1
3 351 00 000
7
71
Phone Line 2 Trouble
LT 2
1 352 00 000
8
82
Phone Line 2 Trouble Restore
LR 2
3 352 00 000
7
72
Data Lost
RT 0
1 354 00 000
8
88
Automatic Test (Normal)
RP
1 602 00 000
9
30
Automatic Test (Off Normal)
RY
1 608 00 000
9
39
Manual Test
RX 0
1 601 00 000
9
99
Test Activation
FX pppp
1 611 0p ppp
9
91
Gas Alarm
GA pppp
1 151 0p ppp
0
03
Gas Alarm Restore
GH pppp
3 151 0p ppp
2
23
Communications Fail YC 1 350 00 000 8 84
System Reset
OR 0
1 305 00 000
7
79
Test Begin
FI pppp
1 604 0p ppp
9
90
Test End
FK pppp
3 604 0p ppp
9
92
Mass Notification Alarm
4
PA pppp
1 120 0p ppp
1
11
Mass Notification Alarm Restore
4
PH pppp
3 120 0p ppp
3
31
Mass Notification Trouble
4
PT pppp
1 375 0p ppp
8
83
Mass Notification Trouble Restore
4
PJ pppp
3 375 0p ppp
7
73
MNS1
1
XB pppp
1 789 0p ppp
1
11
MNS1 Restore
1
XC
pppp
3 789 0p
ppp
3
31
MNS2
1
XN pppp
1 788 0p ppp
6
66
MNS2 Restore
1
XP pppp
3 788 0p ppp
7
76
MNS Trouble
1
XU pppp
1 787 0p ppp
8
83
MNS Trouble Restore
1
XV pppp
3 787 0p ppp
7
73
Security
3
TA pppp
1 137 0p ppp
6
68
Security Restore
3
TH pppp
3 137 0p ppp
7
78
Emergency
2, 4
EB pppp
1 785 0p ppp
6
65
Emergency Restore
2, 4
EC pppp
3 785 0p ppp
7
75
Building
2
ZA pppp
1 152 0p ppp
6
65
Building Event Restore
2
ZH pppp
3 152 0p ppp
7
75
“Other”
2
XY pppp
1 786 0p ppp
4
40
“Other” Restore
2
XZ pppp
3 786 0p ppp
5
50
*pppp is the dialer group or zone number

Related product manuals