EasyManua.ls Logo

Siemens FDOOT241-8 - FDOOT Detector Lines Technical Data

Siemens FDOOT241-8
138 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7BSpecifications
54BTechnical data FDOOT221, FDOOT241-x / -Ax
8
120
| 138
007004_t_en_--
2015-11-04
8.1.2 Detector lines
FDnet
Detector line
Operating voltage (modulated) DC 12…33 V
Operating current (quiescent) 190…230 μA
Maximum current connection factor 1
Quiescent current connection factor 1
Address connection factor 1
Separator connector factor 1
Protocol FDnet
Compatibility See 'List of compatibility'
FDOOT241-Ax line separator
Line voltage:
Nominal DC 32 V (= V
nom
)
Minimum DC 12 V (= V
min
)
Maximum DC 33 V (= V
max
)
Voltage at which the line separator opens:
Minimum DC 7.5 V (= V
SO min
)
Maximum DC 10.5 V (= V
SO max
)
Permanent current when switches are closed Max. 1.5 A (= I
C max
)
Switching current (e.g., in the event of a short-
circuit)
Max. 2 A (= I
S max
)
Leakage current when switches are open Max. 1 mA (= I
L max
)
Serial impedance when switches are closed Max. 0.4 Ω (= Z
C max
)
The line separator is closed via an actuation signal from the control panel. Required line voltage: DC 12…33 V (normal range)
FDOOT221 and FDOOT241-x
line separator
Line voltage:
Nominal DC 32 V (= V
nom
)
Minimum DC 12 V (= V
min
)
Maximum DC 33 V (= V
max
)
Voltage at which the line separator opens:
Minimum DC 7.5 V (= V
SO min
)
Maximum DC 10.5 V (= V
SO max
)
Permanent current when switches are closed Max. 0.5 A (= I
C max
)
Switching current (e.g., in the event of a short-
circuit)
Max. 1 A (= I
S max
)
Leakage current when switches are open Max. 1 mA (= I
L max
)
Serial impedance when switches are closed Max. 0.4 Ω (= Z
C max
)
The line separator is closed via an actuation signal from the control panel. Required line voltage: DC 12…33 V (normal range)

Table of Contents