EasyManua.ls Logo

Siemens FDOOT241-8 - Interactive Detector Line Technical Data

Siemens FDOOT241-8
138 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7BSpecifications
54BTechnical data FDOOT221, FDOOT241-x / -Ax
8
127 |
138
Building Technologies
007004_t_en_--
Fire Safety
2015-11-04
Interactive detector line (FDOOT241-A5)
Detector line
Operating voltage (modulated) DC 21…33 V
Operating current (quiescent) Typ. 220 µA
Maximum current connection factor 1
Address connection factor 1
Separator connector factor 1
Protocol K1151 (interactive)
Compatibility See 'List of compatibility'
Line separator
Line voltage:
Nominal DC 32 V (= V
nom
)
Minimum DC 21.2 V (= V
min
)
Maximum DC 33 V (= V
max
)
Voltage at which the line separator opens:
Minimum DC 14.9 V (= V
SO min
)
Maximum DC 11.2 V (= V
SO max
)
Permanent current when switches are closed Max. 0.11 A (= I
C max
)
Switching current (e.g., in the event of a short-
circuit)
Max. 0.20 A (= I
S max
)
Leakage current when switches are open Max. 1 mA (= I
L max
)
Serial impedance when switches are closed Max. 0.55 Ω (= Z
C max
)
Voltage at which the line separator closes
Minimum DC 15.5 V (= V
SC min
)
Maximum DC 19.5 V (= V
SC max
)
External alarm indicators
External alarm indicators which can be
connected
2
Voltage DC 10…17 V
Current 9…15 mA
Flashing interval times:
Bright 20 ms
Dark 1.5 s (typical)

Table of Contents