Ethernet switch in the Ethernet network
4
20 | 34
Ring wiring with Ethernet module (electric) VN2001
Figure 13: Example of ring wiring with electrical Ethernet (simplified representation)
Jumper settings on the VN2001 for electrical Ethernet:
Switch VN2001 in port P0 VN2001 in port P1
1 open Ground fault supervision
2 open Ground fault supervision
3 open Ground fault supervision
4 open Ground fault supervision
5 open Ground fault supervision
The minimum cable length for an electrical 10/100BaseT cable on the VN2001 is
10 ft/3 m. Shorter lengths are only permitted within the same housing, or if the
connection does not need to be supervised in accordance with the UL864 standard.