9
32 | 34
9 Technical data
Supply Operating voltage DC 24 V
Standby power consumption 95 mA @24 V
Built-in power consumption, supply via
MoNetBus or AUX power
Max. 380 mA @ 24 V
Power consumption via PoE Max. 185 mA @ 24 V
Ethernet interfaces Sockets 4x RJ45, 10/100 Mbit/s
Length of line Max. 100 m via FC TP standard cable
Connectors External supply input 4-pin plug-in terminal
Fault terminal 4-pin plug-in terminal
● Fault output 'F1', 'F2' Dry contact relay (common)
Switching current max. 1 A, resistive
Switching voltage max. DC 30 V
MoNetBus 22-pin flat-cable connector
External Ethernet connections 'P2', 'P3' ● Additional voltage surge protection
● Increased EMC protection
● Ground fault supervision
Circuits ● All connections are power limited
● All connections – except local and
MoNet connections – are supervised
Module connections
(optional)
Ethernet module (electric) VN2001 RJ45 connection (TP), cable length max.
330 ft/100 m
Ethernet module (MM) VN2002 LC connector, multi-mode fiber optic
● Fiber length 62.5/125°µm:
13123 ft/4 km with an 11 dBm loss
1
● Fiber length 50/125°µm: 6561 ft/2 km
with a 7.5 dBm loss
1
Ethernet module (SM) VN2003 LC connector, single-mode fiber optic:
● Fiber length 9/125°µm:
131233 ft/40 km with a 29 dBm loss
1
Mechanical data Dimensions (W x H x D), with cover,
without optional modules
165 x 121 x 43 mm
Weight 560 g/1.2 lbs
Ambient conditions For indoor use in dry rooms only
Operating temperature 120+/-3°F to 32+/-3°F
Rel. humidity during operation 93+/-2% at a temperature of 90+/-3°F
Protection category IP30
1
The length is a guide value dependent upon the loss of the optical cable